Installation; Prevent Electrostatic Discharge; Power; Cabling And Termination - QTS AN-X2-ABDHRIO User Manual

Remote i/o hmi interface module
Hide thumbs Also See for AN-X2-ABDHRIO:
Table of Contents

Advertisement

Prevent Electrostatic Discharge

The module is sensitive to electrostatic discharge.
WARNING!

Power

AN-X requires DC power input of anywhere from 12 to 24 VDC
Left to right the pins on the power connector are chassis ground, negative voltage and
positive voltage. Pin 1 is closest to the Ethernet connector.
The chassis ground should be connected.
Power consumption internally is 200 mA @ 12VDC or 100 mA @ 24VDC.
The part number for the power connector is Phoenix MSTB 2.5/3-ST-5.08

Cabling and Termination

Follow Allen-Bradley cabling recommendations for remote I/O. Refer to Approved
Vendor List for DH, DH+, DH-485, and Remote I/O Cables, publication ICCG-2.2,
February 1996.
On the AN-X module, the remote I/O connections should be line 1, shield, line 2.
AN-X2-ABDHRIO Remote I/O HMI Interface Page
Electrostatic discharge can damage integrated circuits or
semiconductors. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential
Do not touch the connector pins
5

Installation