Chapter 5 Operation

5.1 Check Before Operation

5

5.2 Starting

5.3 Stopping

5.4 Memory Clear (FN711)

60
Before switching power on and starting the product, check the switch settings, installation
and wiring again that they conform to the instructions given in this Operation Manual and
the Manual for Monitoring and Control Network Installation and Wiring (6F8C0880).
If any error is found, correct it according to these manuals.
(1) Checking the switch settings: Check the switch settings using the Engineering tool.
(Host ID setting switches, operation mode setting switches)
(2) Installation check: Check the installation, referring to the Manual for Monitoring and
Control Network Installation and Wiring.
(3) Wiring check: Check the wiring, referring to the Manual for Monitoring and Control
Network Installation and Wiring.
The system starts operating automatically when power is switched on.
When the EN7 or FN modules start, check that they are operating normally, referring to
Table 2-1 (page 9) in Chapter 2.
If the modules fail to start, or if their operation is not normal, stop use and contact the
nearest Toshiba service office.
The system stops when power is switched off.
This section describes the method of clearing all memory areas of the FN module. Do not
perform memory clear while the FN module is in normal operation.
It is to be done when the FN module has been assembled and installed, or replaced, or
when it is to be initialized after error down.
Take the following steps to clear the memory of the FN module backed up by the battery.
(1) Switch the FN module off.
(2) Set only the initializing switches 1 and 2 on the FN module to the ON
position.
(3) Switch the FN module back on, and wait till the HLTH-LED on the
module blinks.
(4) Set all the initializing switches on the FN module back to the OFF
(normal operation) position.
(5) Load user application information.
model 3000 Ethernet Module / DS Connection Module Operation Manual