Connect The Control Cables - ABB ACS580-01 Series Quick Installation And Start-Up Manual

Hide thumbs Also See for ACS580-01 Series:
Table of Contents

Advertisement

Connect the control cables

See figure
F
on page 33. It shows an example with one analog signal cable and one
digital signal cable. Make the connections according to the macro in use. The default
connections of the ABB standard macro are shown in section
on page 16.
Example of connecting an analog signal cable:
1. Cut an adequate hole into the rubber grommet and slide the grommet onto the
cable. Slide the cable through a hole of the bottom plate and attach the grommet
to the hole.
2. Ground the stripped outer shield of the cable 360 degrees under the grounding
clamp. Keep the cable otherwise unstripped as close to the terminals of the
control board as possible. For analog signal cables, ground also the pair-cable
shields and grounding wire at the SCR1 terminal. Secure the cables mechanically
at the clamps below the control board.
3. Route the cable as shown in the figure.
4. Connect the conductors to the appropriate terminals of the control board and
tighten to 0.5...0.6 N·m (0.4 lbf·ft).
5. Tie all control cables to the provided cable tie mounts.
6. Put the unused rubber grommets to the holes in the lead-through plate.
EN – R6...R9 Quick installation guide 15