ABB ACS580-01 Quick Installation And Start-Up Manual

Hide thumbs Also See for ACS580-01:

Advertisement

ABB GENERAL PURPOSE DRIVES
ACS580-01 drives
Quick installation and start-up guide
This guide is applicable to the global product types. There is a separate guide for the North American product types.
Documentation in other languages
Safety instructions
WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If
you are not a qualified electrical professional, do not do electrical installation or maintenance work.
Do not do work on the drive, motor cable, motor, or control cables when the drive is connected to the input power.
Before you start the work, isolate the drive from all dangerous voltage sources and make sure that it is safe to start the
work. Always wait for 5 minutes after disconnecting the input power to let the intermediate circuit capacitors
discharge.
Do not do work on the drive when a rotating permanent magnet motor is connected to it. A rotating permanent
magnet motor energizes the drive, including its input and output terminals.
Frames R1...R2, IP21
(UL Type 1): Do not lift the
drive by holding it from the
cover. The cover can come
loose and cause the drive to
fall.
Frames R5...R9: Do not tilt the
drive. The drive is heavy and
has a high center of gravity. It
can topple accidentally.
Frames R5...R9: Lift the drive
with a lifting device. Use the
lifting eyes of the drive.
1. Unpack the delivery
Keep the drive in its package until you are ready to install it. After unpacking, protect the drive from dust, debris and
moisture. Make sure that these items are included:
cable box (frames R1...R2 and R5...R9, IP21 [UL Type 1])
drive
mounting template
control panel
quick installation and start-up guide
multilingual residual voltage warning stickers
hardware and firmware manuals, if ordered
options in separate packages, if ordered.
Make sure that there are no signs of damage to the items.
2. Reform the capacitors
If the drive has not been powered up for a year or more, you must reform the DC link capacitors. Refer to
reforming instructions
(3BFE64059629
Ecodesign information (EU 2019/1781)
R1...R2
R5...R9
[English]).
About this document
3AXD50000527052 Rev A EN
2021-04-30
© 2021 ABB. All rights reserved.
Original instructions.
R5...R9
Capacitor
1

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS580-01

  • Page 1 Ecodesign information (EU 2019/1781) About this document 3AXD50000527052 Rev A EN 2021-04-30 © 2021 ABB. All rights reserved. Original instructions. Safety instructions WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If you are not a qualified electrical professional, do not do electrical installation or maintenance work.
  • Page 2: Install The Drive On The Wall

    Select the power cables. Obey the local regulations. • Input power cable: ABB recommends to use symmetrical shielded cable (VFD cable) for the best EMC performance. • Motor cable: Use symmetrical shielded cable (VFD cable) for the best EMC performance. Symmetrical shielded cable also reduces bearing currents, wear, and stress on motor insulation.
  • Page 3 R1…R4 R6…R9 × 2 × 2 × 2 × 2 × 4  Frames R1…R4: Put the drive on the wall and tighten the screws  Frame R5, IP21 (UL Type 1): Install the cable box 3×M5...
  • Page 4: Remove The Cover(S)

     Frames R5…R9: Put the drive on the wall and tighten the screws R6…R9 6. Remove the cover(s) R1…R4, IP21 (UL Type 1) R5, IP21 (UL Type 1) R5, IP21 (UL Type 1) R6…R9, IP21 (UL Type 1) R1…R9, IP55 (UL Type 12) 7.
  • Page 5 1) A residual current device must be installed in the supply system. 2) ABB does not guarantee the EMC category or the operation of the ground leakage detector built inside the drive. 10. Measure the insulation of the power cables and the motor Measure the insulation of the input cable before you connect it to the drive.
  • Page 6: Connection Procedure

    360-degree grounding of the cable shield is required for the motor cable and brake resistor cable (if used). It is also recommended for the input power cable. If necessary, install an external filter (du/dt, common mode, or sine filter). Filters are available from ABB. ...
  • Page 7 • Frames R8…R9: If you use only one conductor, ABB recommends that you put it under the upper pressure plate. If you use parallel power cables, put the first conductor under the lower pressure plate and the second under the upper pressure plate.
  • Page 8 Frames R1…R2, R4, R6…R9: Install the grounding shelf. In frames R6…R9, this is the grounding shelf for the control cables. R1…R2 R6…R9 Frame R5: Install the cable box plate (a) and shroud (b). Attach the cables outside the drive mechanically. Ground the motor cable shield at the motor end.
  • Page 9: Connect The Control Cables

    Ground also the pair-cable shields and grounding wire at the SCR terminal. Tie all control cables to the provided cable tie mounts.  Default I/O connections (ABB standard macro) Reference voltage and analog inputs and outputs Signal cable shield (screen) Ext.
  • Page 10  Control cable installation examples This section shows examples for routing the control cables in frames R4 and R6…R9. Frames R1…R3 and R5 are similar to frame R4. R6…R9  EIA-485 embedded fieldbus connection You can connect the drive to a serial communication link with a fieldbus adapter module or the embedded fieldbus interface.
  • Page 11: Start Up The Drive

    Overview and connection diagrams for connecting the drive to the fieldbus are shown below. Fieldbus controller Termination ON Fieldbus 1) The devices at both ends on the fieldbus must have termination set to ON. 2) One device, preferably at the end on the fieldbus, must have bias set to ON.
  • Page 12: Fieldbus Communication

    PID, fieldbus, advanced functions and clock, region and display. You can also reset logs, parameters, and the control panel Home view. ABB recommends that you make at least these additional settings: • Choose a macro or set start, stop and reference values separately •...
  • Page 13: Warnings And Faults

    3381 Output phase loss All three phases are not connected to the motor. 5090 STO hardware failure STO hardware diagnostics has detected hardware failure. Contact ABB. A5A0 5091 Safe torque off The Safe torque off (STO) function is active. A7CE...
  • Page 14: Terminal Data For The Power Cables

    3) The drive is suitable for use on a circuit capable of delivering not more than 100000 symmetrical amperes (rms) at 480 V maximum when protected by the fuses given in this table. Alternate Fuses, MMPs and Circuit Breakers for ABB Drives 4) Refer to...
  • Page 15: Ambient Conditions

    TT, and IT (ungrounded or high-resistance symmetrically grounded). For the installation requirements for corner-grounded systems at this altitude, contact your local ABB representative. Surrounding air temperature -15 … +50 °C (5 … 122 °F). No frost permitted. The rated output current must be derated by 1% for each 1 °C (1.8 °F) above 40 °C (104 °F).
  • Page 16: Related Documents

    Related documents Document Code (English) ACS580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual 3AXD50000044794 ACS580 standard control program firmware manual 3AXD50000016097 ACx-AP-x assistant control panels user’s manual 3AUA0000085685 Drive composer PC tool user's manual 3AUA0000094606 Declarations of Conformity...

Table of Contents