Installation

Observe these guidelines when installing a field controller:
Transport the controller in the original container to
minimize vibration and shock damage.
Verify that all parts shipped with the controller.
Do not drop the controller or subject it to physical
shock.

Parts Included

one controller with removable terminal blocks (Power
and SA/FC bus are removable)
one installation instructions sheet
Materials and Special Tools Needed
three fasteners appropriate for the mounting surface
(M4 screws or #8 screws)
one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only)
small straight-blade screwdriver for securing wires in
the terminal blocks
Mounting
Observe these guidelines when mounting a field
controller:
Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied enclosure.
Mount the controller horizontally on 35 mm DIN rail
whenever possible.
Mount the controller in the proper mounting position
(see
Figure
1).
Mount the controller on a hard, even surface
whenever possible in wall-mount applications.
Use shims or washers to mount the controller securely
and evenly on the mounting surface.
Mount the controller in an area free of corrosive
vapors and observe the Ambient Conditions
requirements in
Technical
Provide for sufficient space around the controller for
cable and wire connections for easy cover removal
and good ventilation through the controller (50 mm
[2 in.] minimum on the top, bottom, and front of the
controller).
Do not mount the controller on surfaces prone to
vibration, such as duct work.
Do not mount the controller in areas where
electromagnetic emissions from other devices or
wiring can interfere with controller communication.
IOM1711 and IOM2711 Input/Output Module Installation Instructions
Specifications.
Observe these additional guidelines when mounting a
field controller in a panel or enclosure:
Mount the controller so that the enclosure walls do
not obstruct cover removal or ventilation through the
controller.
Mount the controller so that the power transformer
and other devices do not radiate excessive heat to
the controller.
Do not install the controller in an airtight enclosure.
Figure 1: Controller Mounting Positions
DIN Rail Mount Applications
Mounting the controller horizontal on 35 mm DIN rail is
the preferred mounting method.
To mount a field controller on 35 mm DIN rail:
1. Securely mount a 20 cm (8 in.) or longer section of
35 mm DIN rail horizontal and centered in the desired
space so that the controller mounts in the horizontal
position shown in
Figure
2. Pull the bottom mounting clip outward from the
controller to the extended position as shown in
2.
3. Hang the controller on the DIN rail by the hooks at
the top of the (DIN rail) channel on the back of the
controller
(Figure
2), and position the controller snugly
against the DIN rail.
4. Push the bottom mounting clip inward (up) to secure
the controller on the DIN rail.
To remove the controller from the DIN rail, pull the
bottom mounting clip out to the extended position and
carefully lift the controller off the DIN rail.
Wall Mount Applications
To mount a field controller directly on a wall or other flat
vertical surface:
1.