Characteristics, Functions, and Applications
RIPPLE NOISE MEASUREMENT CONDITIONS
L
Output ripple and noise measurement point (20MHz)
C
: 100µF Electrolytic capacitor
1
C
: 0.1µF Film capacitor
2
L
: 150mm
SERIES OPERATION (TO INCREASE OUTPUT VOLTAGE OR
TO OBTAIN SEPARATE ±OUTPUT)
When the output voltage of a single power supply is insufficient,
several power supplies can be connected in series in order to
obtain a higher voltage or separate ±outputs.
If power supplies A and B in the illustration below are 5V each, a
10V output can be obtained in this connection. It should be noted
that, however, the output current is limited to the lower rated cur-
rent value of the power supplies A and B. There is no problem if
the voltages of A and B are different from each other.
D1 and D2 in the illustration designate diodes for preventing
reverse voltage application. They are provided for preventing inter-
nal components of the power supply having the lower rated voltage
from being damaged by an applied reverse voltage caused by a
short circuit in the load or the like.
Use diodes which meet the following requirements:
Reverse withstanding voltage: Over twice that of the combined
output voltage
Forward current: Over twice that of the output current
Forward voltage drop: As small as possible
(e.g. Shottkey diode, etc.)
SERIES CONNECTION FOR INCREASING OUTPUT VOLTAGE
+
Power supply A
D1
(A) ∗
+
Power supply B
D2
∗ For obtaining separate ±outputs, (A) should be zero voltage.
• All specifications are subject to change without notice.
+
C
C
1
2
Load
INSULATION AND WITHSTAND VOLTAGE TESTS
The insulation and withstand voltage tests may cause deteriora-
tion. Care must be taken for execution of the tests. The potential
must be equal among input, output, and FG (frame ground) termi-
nals. It is preferable to use testers that gently start up at the test-
ON and automatically discharge charged energy at the test-OFF.
Manual discharging after the tests should be through a resistor
around 100kΩ to 1MΩ (Do not perform discharging at low imped-
ance. It may cause deterioration.)
In any case, take full countermeasures for electric-shock preven-
tion.
OTHER CONDITIONS
• Unless conditions are otherwise specified in the specifications or
standards, 25°C and rated input-output should be applied.
(18/30)