1 Overview
The ECC-RPU is an optional Remote Page Unit
compatible with the ECC-50/100 Emergency Command
Center. The ECC-RPU provides 8 message select buttons.
The 9th button can be used to activate an MMF-300
monitor module mounted inside the cabinet. The RPU
requires an external data bus connection, an external audio
riser connection, and an external operator interface power
connection (24 volts DC) from the ECC-50/100 main
console. ALL CALL paging can be broadcast over the
speaker circuits by depressing the microphone's push-to-
talk switch. Refer to the ECC-50/100 Manual, LS10001-
000FL-E, for more information.
Figure 1 ECC-RPU
NOTE: Installation and wiring of this device must be
done in accordance with NFPA 72 and local ordinances.
2 Installation
2.1 Removing the Dress Panel
1.
Open the door and lift the door off the pin hinges.
2.
Loosen the screw securing the dress panel to the
backbox.
3.
Open dress panel and disconnect the ground wire
from the back.
4.
Lift up dress panel and pull out lower pivot flange.
Slide the upper pivot flange down to completely
remove the dress panel from cabinet. Store in a safe
location.
ECC-RPU Remote Page Unit
Product Installation Document
PN LS10030-000FL-E:B 8/9/2013 13-696
3. slide down
1. lift up
2. pull out
Figure 2 Removing the Dress Panel
2.2 Mounting the Backbox
1.
Mark and predrill holes for the top two backbox
keyhole mounting bolts using the dimensions shown.
2.
Install two upper fasteners in the wall with the screw
heads protruding.
3.
Using the upper 'keyholes', mount the backbox over
the two screws.
4.
Mark and drill the lower two holes.
5.
Install the remaining fasteners and tighten all
fasteners to complete backbox mounting.
10.0" (25.4cm) O.C.
lower mounting holes
Figure 3 Backbox Mounting
6.
Carefully reinstall the dress panel by reversing the
steps in Section 2.1. Remember to reattach the
ground cable.
7.
Reinstall door.
A trim ring, TR-6-R, is available for semi-flush mount
installations.
One Fire-Lite Place
Northford, CT 06472-1653 USA
203-484-7161 • FAX 203-484-7118
www.firelite.com
screw
location
keyholes

Advertisement

loading

Summary of Contents for Honeywell Fire-Lite ECC-RPU

  • Page 1 One Fire-Lite Place Northford, CT 06472-1653 USA 203-484-7161 • FAX 203-484-7118 www.firelite.com ECC-RPU Remote Page Unit Product Installation Document PN LS10030-000FL-E:B 8/9/2013 13-696 1 Overview 3. slide down The ECC-RPU is an optional Remote Page Unit compatible with the ECC-50/100 Emergency Command Center.
  • Page 2 3 Wiring 2.3 Mounting/Wiring an Optional Monitor Module Connections are made from TB24, TB12, and TB22 on the An MMF-300 monitor module may be mounted inside the ECC-50/100 main control board to TB1, TB3, and TB2 on the RPU. If the ECC-RPU is the last device on the audio cabinet.
  • Page 3: Led Indicators

    5 Slide-in Label ECC main Carefully cut along the outside of the label. Identify external operator interface control board power - 24VDC keypad buttons as desired and slide the label upwards TB24 through the slot at the bottom of the keypad. external data bus TB12...