Unit Positioning - International comfort products FHS Series Installation Instructions Manual

Package air handling units
Table of Contents

Advertisement

MODEL SERIES
Position Number
F = R-410A Fan Coil Unit
A = Air Conditioning (Cooling Only)
H = Heat Pump
S = Standard Efficiency
072 = 6 Tons (1 circuit)
091 = 7.5 Tons (1 circuit)
120 = 10 Tons (2 circuit)
150 = 12.5 Tons (2 circuit) (FAS units only)
180 = 15 Tons (2 circuit)
240 = 20 Tons (2 circuit)
300 = 25 Tons (2 circuit) (FAS units only)
336 = 30 Tons (2 circuit) (FAS units only)
K = 208/230−1−60
H = 208/230−3−60
M = 460/208/230−3−60
L = 460−3−60
S = 575−3−60
A = Standard Static Standard Efficiency Motor / Standard Drive
• 6 to 15 ton 208/230v, 460v, 575v-3-60, 6 and 7.5 ton 208/230-1-60, 1-speed
• all 2-speed
B = High Static Standard Efficiency Motor / High Drive
• 6 to 15 ton 208/230V, 460v, 6 to 10 ton 575v-3-60, 1-speed
• all 2-speed
D = Standard Static High Efficiency Motor / Standard Drive
• 20, 25, 30 ton all 3 phase
E = High Static High Efficiency Motor / High Drive
• 15 to 30 ton all 3 phase
A = Cu/Al
A = Future Use
0 = Single Speed Indoor Fan Motor
2 = Two Speed Indoor Fan Motor Controller (VFD)
A = Standard - Unpainted
B = Painted cabinet (Gray)
0 = Future Use
A = Standard
Notes:
• All FAS072-150 units and FHS 072-120 units with a "M" voltage designation are triple voltage; i.e., 208/230/460-3-60.
FAS 180 units are also triple voltage in the "M" configuration unless the High Static motor option is used.
"M" voltage is not available on 2-speed indoor fan motor option.
• Single-phase 072 and 091 units designate standard motor and high static drive.

Unit Positioning

The unit can be mounted on the floor for vertical applica-
tion with return air entering the face of the unit and supply
air discharging vertically through the top of the unit. The
unit can also be applied in a horizontal arrangement with
return air entering horizontally and the supply air discharg-
ing horizontally. When applying the unit in a horizontal ar-
rangement, ensure the condensate drain pan is located at
the bottom center of the unit for adequate condensate dis-
posal. See Fig. 6 for condensate connections for each unit
position.
14
F
A
S
0
1
2
3
4
Type
Efficiency
Nominal Tonnage
Fig. 4 — Model Number Nomenclature
Typical positioning and alternate return air locations are
shown in Fig. 6. Alternate return air locations can be used
by moving the unit panel from the alternate return air loca-
tion to the standard return air location. Refer to overhead
suspension accessory drawing (Fig. 7) for preferred sus-
pension technique. The unit needs support underneath to
prevent sagging.
Specifications subject to change without notice.
9
1
M
A
A
5
6
7
8
9
Voltage
Fan Motor Options
Painted Cabinet Options
IMPORTANT: Do NOT attempt to install unit with
return air entering top panel of unit. Condensate will
not drain from unit.
A
0
A
0
A
12
14
13
10
11
Future Use
508 01 1603 01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents