34. PRESSURE SERVICE PORTS

High and low pressure service ports are installed on
all units so that the system operating pressures can
be observed. Table 12 outlines expected pressures at
various indoor and outdoor temperatures.
This unit employs high-flow Coremax valves instead of
the typical Shrader type valves.
High Capacity Cooling
Return Air
Model
Temperature
75° DB
62° DB
80° DB
WG3S2
67° DB
85° DB
72° DB
75° DB
62° DB
80° DB
WG4S2
67° DB
85° DB
72° DB
75° DB
62° DB
80° DB
WG5S2
67° DB
85° DB
72° DB
Low Capacity Cooling
Return Air
Model
Temperature
75° DB
62° DB
80° DB
WG3S2
67° DB
85° DB
72° DB
75° DB
62° DB
80° DB
WG4S2
67° DB
85° DB
72° DB
75° DB
62° DB
80° DB
WG5S2
67° DB
85° DB
72° DB
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Cooling Pressures (All Temperatures °F)
Pressure
50
55
60
Low Side
112
115
119
High Side
195
214
233
Low Side
124
127
131
High Side
201
220
239
Low Side
135
138
142
High Side
205
224
243
Low Side
117
119
121
High Side
197
216
235
Low Side
127
129
131
High Side
201
220
239
Low Side
141
143
145
High Side
203
223
243
Low Side
118
119
120
High Side
199
217
236
Low Side
129
130
131
High Side
205
224
247
Low Side
137
139
140
High Side
216
237
258
Pressure
50
55
60
Low Side
126
127
129
High Side
181
198
215
Low Side
134
134
135
High Side
184
201
218
Low Side
153
154
155
High Side
190
207
224
Low Side
122
124
125
High Side
184
201
218
Low Side
132
134
136
High Side
185
203
221
Low Side
145
147
149
High Side
187
205
223
Low Side
123
125
127
High Side
187
207
226
Low Side
134
136
138
High Side
192
211
230
Low Side
146
148
149
High Side
200
217
235
WARNING! Do NOT use a Schrader valve core removal
tool with these valves. Use of such a tool could result
in eye injuries or refrigerant burns!
To change a Coremax valve without first removing the
refrigerant, a special tool is required which can be
obtained at www.fastestinc.com/en/SCCA07H. See the
replacement parts manual for replacement core part
numbers.
TABLE 12
Air Temperature Entering Outdoor Coil °F
65
70
75
80
122
126
129
131
253
272
291
314
134
138
139
140
259
278
297
319
145
149
152
154
263
282
301
326
123
125
127
128
255
274
293
316
134
136
138
138
259
278
298
318
148
150
152
152
263
283
303
326
122
123
125
126
260
285
309
333
131
132
132
134
270
292
315
339
141
142
143
146
279
300
321
346
Air Temperature Entering Outdoor Coil °F
65
70
75
80
130
132
133
135
233
250
267
289
135
136
136
137
236
253
270
291
156
157
158
160
241
258
275
297
127
129
131
131
236
254
272
291
138
140
142
145
239
257
275
298
152
154
156
156
241
259
278
397
129
131
133
134
245
263
282
305
139
141
143
144
248
267
286
308
151
152
154
156
252
270
287
311
85
90
95
100
132
134
135
136
337
360
383
409
140
141
141
148
341
363
389
413
156
157
159
161
350
375
399
425
130
131
132
133
339
361
383
410
139
139
145
145
341
364
381
415
153
153
154
156
349
372
396
422
128
129
130
132
357
381
405
432
137
139
143
143
363
387
394
438
148
151
153
155
370
395
419
447
85
90
95
100
136
138
139
141
310
332
353
378
137
138
138
140
312
333
358
380
162
163
165
167
318
340
361
387
132
133
134
135
312
335
359
381
146
147
149
149
317
339
354
384
157
158
159
161
319
343
369
390
135
136
137
139
328
350
373
399
145
146
148
153
331
353
367
402
159
161
163
165
335
358
382
408
Manual
Page
105
110
115
138
139
140
435
461
487
149
151
152
440
468
495
162
164
165
451
476
502
135
136
137
438
466
494
146
146
149
443
471
500
158
160
162
449
478
508
133
135
136
460
487
514
145
146
148
465
492
519
157
158
160
474
502
529
105
110
115
144
146
148
404
429
454
142
144
146
406
432
458
168
170
171
413
438
464
137
139
141
407
435
463
150
151
152
410
438
467
163
164
165
415
443
472
141
143
145
425
451
477
155
156
158
429
456
483
166
168
169
434
460
486
2100-587J
45 of 59