ADJUSTMENT OF MANIFOLD GAS PRESSURE &
INPUT RATE
Inlet and manifold gas pressure may be measured by connecting the
"U" tube manometer to the gas valve with a piece of tubing. Follow the
appropriate section in the instructions below. Refer to Figure 17 for a
drawing of the locations of the pressure ports on the gas valve.
Turn gas off at the ball valve or gas cock on gas supply line
before the gas valve. Find the pressure ports on the gas
valve marked Out P and In P.
1. The manifold pressure must be taken at the port marked OUT P.
2. The gas line pressure must be taken at the port marked IN P.
3. Using a 3/32" (2.4 mm) hex head wrench, loosen the set screw by
turning it 1 turn counter clockwise. DO NOT REMOVE THE SET
SCREW FROM THE PRESSURE PORT.
Read the inlet gas pressure
Connect the positive side of the manometer to the IN P Tap on the gas
valve. Do not connect any tubing to the negative side of the manometer,
as it will reference atmospheric pressure. Refer to Figure 18 for connec-
tion details.
1. Turn gas and electrical supplies on and follow the operating instruc-
tions to place the unit back in operation.
Table 9: Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

Minimum*
Natural Gas
4.5" W.C. (1.12 kPa)
IMPORTANT: The inlet gas pressure operating range table specifies
what the minimum and maximum gas line pressures must be for the
furnace to operate safely. The gas line pressure MUST BE a mini-
mum of:
• 7" w.c. (1.74 kPA)
in order to obtain the BTU input specified on the rating plate and/or
the nominal manifold pressure specified in these instructions and on
the rating plate.
2. Once the correct gas inlet pressure has been established, see
Table 9, turn the gas valve to OFF and turn the electrical supply
switch to OFF; then remove the flexible tubing from the gas valve
pressure tap and tighten the pressure tap plug using the 3/32" (2.4
mm) hex head wrench.
3. Turn the electrical and gas supplies back on, and with the burners
in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved non-corrosive gas leak detec-
tion fluid, or other non-flammable leak detection methods.
Read the manifold gas pressure
Connect the positive side of the manometer to the OUT P Tap on the
gas valve. Do not connect any tubing to the negative side of the
manometer, as it will reference atmospheric pressure. Refer to Figure
18 for connection details.
IMPORTANT: The cap for the pressure regulator must be removed
to gain access to the adjustment screw. Loosening or tightening the
cap does not adjust the flow of gas.
1. Refer to Figure 17 for location of pressure regulator adjustment cap
and adjustment screws on main gas valve.
2. Turn gas and electrical supplies on and follow the operating instruc-
tions to place the unit back in operation.
16
3. Adjust manifold pressure by adjusting gas valve regulator screw for
Table 10: New: Nominal Manifold Pressure
FIGURE 17: Gas Valve
IMPORTANT: If gas valve regulator is turned in (clockwise), manifold
pressure is increased. If screw is turned out (counter clockwise),
manifold pressure will decrease.
4. After the manifold pressure has been adjusted, re-calculate the fur-
Maximum
10.5" W.C. (2.61 kPa)
5. Once the correct BTU (kW) input has been established, turn the
6. Turn the electrical and gas supplies back on, and with the burners
IGNITER
FIGURE 18: Reading Gas Pressure
the appropriate gas per the following:
NOMINAL MANIFOLD PRESSURE
Natural Gas
OUTLET
PRESSURE
PORT
INLET
WRENCH
BOSS
INLET
PRESSURE
ON/OFF SWITCH
PORT
(Shown in ON position)
nace input to make sure you have not exceeded the specified input
on the rating plate. Refer to "CALCULATING THE FURNACE
INPUT (NATURAL GAS)".
gas valve to OFF and turn the electrical supply switch to OFF; then
remove the flexible tubing from the gas valve pressure tap and
tighten the pressure tap plug using the 3/32" (2.4 mm) hex head
wrench.
in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved non-corrosive gas leak detec-
tion fluid, or other non-flammable leak detection methods.
MANIFOLD PRESSURE "U" TUBE CONNECTION
AUX.
LIMIT
SWITCH
GAS
VALVE
BURNER
ASSEMBLY
U-TUBE
MANOMETER
Johnson Controls Ducted Systems
3.5" w.c. (0.87 kPa)
VENT PORT
OUTLET
MAIN REGULATOR
ADJUSTMENT
A0226-001
FLAME
SENSOR
¼" TUBING
OUTLET
PRESSURE
TAP
3.5" GAS
PRESSURE
SHOWN
A1103-001