Auto Start Volt; Auto Stop Load; Load Limit; Delay (Seconds) - Kohler 6VSG Installation Instructions Manual

Dc generator sets
Hide thumbs Also See for 6VSG:
Table of Contents

Advertisement

1.13.2 Auto Start Volt

This value is the voltage at which the 6VSG will
automatically start. The automatic start criteria are
met when this voltage has reached or fallen below this
value for the specified delay period (standard
3 minutes, only changed using SiteTech).
voltage is detected at the generator and may differ
from the voltage measured at the load or the battery
due to voltage drop in the lines.
Figure 1-25
6VSG-24V
Default
25 VDC
Minimal value
15 VDC
Maximal value
60 VDC
Figure 1-24 Auto Start Voltage Settings

1.13.3 Auto Stop Load

This value is the load level at which the 6VSG will
automatically stop. The automatic stop criteria are met
when the load has reached or fallen below this value
for the specified delay period (standard 3 minutes and
only changed using SiteTech). This load is detected at
the generator.
Figure 1-26
6VSG-24V
Default
40%
Minimal value
0%
Maximal value
100%
Figure 1-25 Auto Stop Load Settings

1.13.4 Load Limit

This value is the limit to the generator capacity. This
allows the 6VSG to limit current output to the
maximum charge rate specified by the battery
manufacturer or load in the application. Adjustments
should be done by qualified individuals after referring
to battery manufacturer's recommended maximum
charge rate.
Figure 1-27
6VSG-24V
Default
100%
Minimal value
0%
Maximal value
120%
Figure 1-26 Load Limit
(Charge voltage x Charge current)
Load limit =
TP-6842 7/15
This
6VSG-36V
6VSG-48V
37.5 VDC
50 VDC
15 VDC
15 VDC
60 VDC
60 VDC
6VSG-36V
6VSG-48V
40%
40%
0%
0%
100%
100%
6VSG-36V
6VSG-48V
100%
100%
0%
0%
120%
120%
60

1.13.5 Delay (seconds)

This delay is used to determine the amount of time a
value (Auto Start Volt or Auto Stop Load) needs to be
sustained before the respective action is taken
pertaining to the value.
changed using a personal computer (laptop) and
Kohler SiteTech software.
Kohler distributor or dealer to adjust the setting, if
necessary.
Figure 1-28
6VSG-24V
Default
3 minutes
Minimal value
1 second
Maximal value
60 minutes
Figure 1-27 Auto Start/Auto Stop Delay Settings
The delay can only be
Contact an authorized
6VSG-36V
6VSG-48V
3 minutes
3 minutes
1 second
1 second
60 minutes
60 minutes
Section 1 Installation
25