16. Troubleshooting Guide

Controller is powered but does not turn on
Fuse has blown
Controller cannot communicate on an FTT network
Absent or incorrect supply voltage
Network not wired properly
Absent or incorrect network termination
Incorrect APB file has been downloaded
Service pin not working
Controller communicates well over a short network, but does not communicate on large network
Network length
Wire type
Network wiring problem
Absent or incorrect network termination
Extra capacitance
Number of controllers on network
segment exceeded
Network traffic
Hardware input is not reading the correct value
Input wiring problem
Open circuit or short circuit
Configuration problem
Hardware output is not operating correctly
Output wiring problem
Configuration problem
Controller resets periodically
Short circuit between 24VAC OUT and
COM
Service LED (Orange Color)
Off
On
Slow Blink
(1 sec. On, 1 sec. Off)
Fast Blink
(0.3 sec. On, 1 sec. Off)
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners.
© 2009 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc.
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
U.S.A.
Check the fuse integrity. If the fuse has blown, perform the following:
1. Turn off power from the controller.
2. Remove the front plate of the controller. The fuse is located close to the power terminals.
3. Replace the fuse with a 2A fast-acting high-breaking capacity fuse (1500A @ 250VAC). Dimensions: 5
x 20mm.
4. Reattach the front plate to the controller.
1. Check power supply voltage between the 85-265VAC and NEUTRAL pins and ensure that it is within
acceptable limits.
2. Check for a tripped fuse or circuit breaker.
Double check that the wire connections are correct.
Check the network termination(s).
Use the memory erase jumper to reset the Neuron chip's memory.
Use the memory erase jumper to reset the Neuron chip's memory.
Check that the total wire length does not exceed the specifications of the Junction Box and Wiring
Guideline for Twisted Pair LonWorks Networks.
Check that the wire type agrees with the specification of the Junction Box and Wiring Guideline for Twisted
Pair LonWorks Networks.
Double check that the wire connections are correct.
Check the termination(s). Incorrect or broken termination(s) will make the communication integrity
dependent upon a controller's position on the network.
Make sure that no extra capacitance is being connected to the network other than the standard FTT circuit
and a maximum of a 3 meter stub (in bus topology).
The number of controllers on a channel should never exceed 64. Use a router or a repeater in accordance
to the Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks.
Query node statistic to check errors.
Use a LON protocol analyzer to check network traffic.
Check that the wiring is correct according to this document and according to the peripheral device's
manufacturer.
Use a voltmeter, check the voltage on the input terminal. Short circuit (0V) and open circuit (5V).
Use the controller configuration plug-in to check the configuration of the input. Refer to the controller's user
guide for more information.
Check that the wiring is correct according to this manual and according to the peripheral device's
manufacturer.
Use the controller configuration plug-in to check the configuration of the output. Refer to the controller's
user guide for more information.
Make sure that the 24VAC OUT is not connected to the COM.
The controller is in normal operation or not powered (if the controller is powered and the LED is off, pressing
the Service Pin will light up the LED).
The controller is application-less.
Appropriate action: Reload the application file (.apb).
The controller is unconfigured.
Appropriate action: Commission the controller.
Watchdog time out. Application corrupted.
Appropriate action: Use the memory erase jumper to reset the Neuron chip's memory, and then load the
proper APB into the controller using a network management tool (e.g. LMT).