ABB PST Series Installation And Commissioning Manual page 160

Table of Contents

Advertisement

&KDSWHU 
7URXEOH VKRRWLQJ
6WDWXV
Displayed current in LCD does
not correspond to motor current.
Displayed current in LCD is not
stable.
Loading of parameters does
not work properly.
6WDWXV
Power on
Fault
Protection
Power on
Fault
Protection
160
3RVVLEOH FDXVH
Inside Delta connection.
The motor is too small.
Theload on the motor is too
small.
(current is out of measuring
range).
Fieldbus settings.
 6WDUW XS IDXOWV
3RVVLEOH FDXVH
LCD Auto shut off the keypad.
Supply voltage is not connected.
6ROXWLRQ
• If the softstarter is connected Inside
Delta, the current displayed is 58%
e
(
1
3
) of the motor current.
• Check that the softstarter corresponds
to the motor size.
• Increase the load if possible.
• Check that softstarter and motor sizes
correspond.
• See chapter Fieldbus for actual field-
bus type.
6ROXWLRQ
• Touch any key on the keypad.
• Connect the Supply voltage according to
the circuit diagram.
1SFC132003M0201