ABB PST Series Installation And Commissioning Manual page 121

Table of Contents

Advertisement

U
70%
30%
Start
)LJXUH  ,QLWLDO YROWDJH IRU 6WDUW UDPS
U
100%
70%
30%
Stop
)LJXUH  (QG YROWDJH IRU 6WRS UDPS
1SFC132003M0201
 ,QLWLDO YROWDJH
3DWK LQ PHQX
0HQX6(77,1*6)XQFWLRQDO 6HWWLQJV
6WDUW6WRS  ,QLW 9ROW
This parameter makes it possible to set the voltage level
where the start ramp begins. If the initial voltage is set too
low, it will only cause longer starting time and unnecessary
heating of the motor.
3DUDPHWHU
'HIDXOW YDOXH 6HWWLQJ UDQJH
WH[W
Init Volt
30%
 (QG YROWDJH
3DWK LQ PHQX
0HQX6(77,1*6)XQFWLRQDO 6HWWLQJV
6WDUW6WRS  (QG 9ROW
This parameter makes it possible to set the voltage level
where the stop ramp ends. This function will be active only
if parameter Stop ramp is used.
3DUDPHWHU
'HIDXOW YDOXH 6HWWLQJ UDQJH
WH[W
End Volt
30%
&KDSWHU 
)XQFWLRQV
'HVFULSWLRQ
30...70%
Initial voltage
for stop ramp
'HVFULSWLRQ
30...70%
End voltage for
stop ramp
121