Installing Easyair Sns300 With Ceiling Mount Bracket (Sns300Cmp) - Philips EasyAir SNS300 Design-In Manual

Hide thumbs Also See for EasyAir SNS300:
Table of Contents

Advertisement

Installing EasyAir SNS300 with ceiling mount bracket (SNS300CMP)

The ceiling mount bracket SNS300CMP is premounted with the EasyAir SNS300 and the cable. The strain relief
is already part of the CMP300.
Drill 63.5 mm hole in the ceiling for installation of the SNS300CMP bracket. For more details on cut-out and
mounting, refer the figures below. All dimensions are in mm.
Connect the wires from the sensor to the LED Driver in the luminaire. Connect the white wire from the sensor to
the SR- terminal and the red wire from the sensor to the SR+ terminal of the SR driver. Follow luminaire
manufacturer's instructions for accessing the SR driver.
The EasyAir SNS300 operates upon energization with no further commissioning. See the chapter "Lighting
Control" for configuring parameters during or after installation. Refer EasyAir SNS300 App Manual to configure
the sensor using the Philips Field Apps.
Radius min 5 mm
17
Design-in Guide - EasyAir SNS300
April 2019
August, 2019

Advertisement