Pressure Relief Pipe Work - Worcester GB162-50 V2 Installation, Commissioning And Servicing Instructions

Commercial wall hung gas fired condensing boilers
Table of Contents

Advertisement

14
*
1
7
Fig. 19 Condensate pump to external disposal
[1]
Condensate discharge from boiler
[7]
Condensate pump
[13] Insulate and increase pipe size
[14] Pipe work transition
[*]
Condensate trap of 75mm already incorporated into the boiler
3.6

Pressure relief pipe work

NOTICE:
▶ The pressure relief valve is a safety device for the boiler and if
activated may discharge boiling water or steam through the relief
valve drain pipe.
▶ Care should be taken when siting the outlet pipe so that it does not
cause an obstruction or discharge above a window, entrance or other
public access where it could cause a hazard.
• The pressure relief drain pipe (1) from the boiler should be the same
diameter as the outlet of the safety valve, copper pipe, and run
downwards, away from any electrical equipment or other hazard,
preferably to an external drain or soak away.
• In domestic installations pressure relief drain pipe (1) should be
finished with a partial bend, near the outlet to face the external wall
(as shown) to help prevent freezing.
• In commercial installations an internal drain in the plant room can be
used for both the pressure relief and condensate discharge.
Worcester Commercial Boiler Series – 6720814332 (2019/04)
13
25mm min.
0010025991-001
Fig. 20 Pressure relief pipe work
[1]
[2]
[3]
[4]
Combined PRV and condensate
The PRV and condensate discharge can be combined by the installer on
the 50kW and 65kW models only according to BS 6798. However, care
must be taken to ensure that an air gap is present between the PRV
discharge pipe and the connection to the condensate discharge pipe.
This is to guard against any potential blockage of the PRV, for example,
frozen condensate.
If the system pressure exceeds the maximum pressure this will result in
the volume of water being discharged through the PRV to be greater than
the storage capacity of condensate pumps.
DO NOT fit a condensate pump when combining the PRV and
condensate.
1
2
3
4
Drain pipe
Outside wall
Drain pipe
External drain
Pre-Installation
0010025992-001
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gb162-65 v2Gb162-100 v2Gb162-85 v2

Table of Contents