Local Equipment Network; Board Addresses; Control Module Communication; Carrier Comfort Network® Interface - Carrier AquaForce B Series Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Variable speed air-cooled liquid chillers with greenspeed intelligence and carrier controller
Table of Contents

Advertisement

IN/OUT
CHANNEL
TYPE
CH 01
AI
CH 02
AI
CH 03
AI
CH 04
AI
CH 05
AI
CH 06
AI
CH 07
AO
CH 08
DI
CH 09
DI
CH 10
DI
CH 11a
DI
CH 11b
DI
CH 12
DI
CH 13
DI
CH 14
DI
CH 15
DI
CH 16
DO
CH 17
DO
CH 18
DO
CH 19
DO
CH 20
DO
CH 21
DO
CH 22
DO
CH 23
DO
CH 24
DO
CH 25
DO

Local Equipment Network

Information is transmitted between modules via a 3-wire com-
munication bus or LEN.

Board Addresses

All boards (except the Carrier Controller display and the Energy
Management Module) have DIP switches to set the address.

Control Module Communication

RED LED
Proper operation of the control boards can be visually checked
by looking at the red status LEDs (Light-Emitting Diodes).
When operating correctly, the red status LEDs will blink in
unison at a rate of once every 2 seconds. If the red LEDs are
not blinking in unison, verify that correct power is being sup-
plied to all modules and that all communication wiring is con-
nected securely. Confirm current version of software installed
on SmartView panel by navigating to Control Identification
Menu (Main Menu
Configuration Menu
uration Menu
Control Identification Menu
Part Number). If a newer version of the software exists, con-
tact your Carrier service representative service to reload current
software. If the problem still persists, replace the Carrier Con-
troller module. A red LED that is lit continuously or blinking at
a rate of once per second or faster indicates that the board
should be replaced.
GREEN LED
All boards have a green LEN LED which should be blinking
whenever power is on. If the LEDs are not blinking as de-
scribed check LEN connections for potential communication
errors at the board connectors. A 3-wire bus accomplishes
Table 12 — EMM Board Inputs and Outputs
BOARD
CCN POINT
CONNECTOR
SPACETMP
J6
J7A
SP_RESET
J7B
LIM_ANAL
J8
CAP_T
J4, CH8
OCC_OVSW
J4, CH9
LIM_SW2
J4, CH10
REM_LOCK
J4, CH11A
ICE_SW
J4, CH11B
J5, CH12
J5, CH13
J5, CH14
J5, CH15
J2A
CP_A
J2A
CP_B
J2A
J2A
J2B
J2B
J2B
J2B
J3
SHUTDOWN
J3
ALERT
HMI Config-
Software
POINT
DESCRIPTION
Space temperature
Setpoint reset
Capacity limit
% Total capacity running
Occupancy override
Demand limit SW2
Remote lockout switch
Ice done
Compressor A run status
Compressor B run status
Shutdown relay
Alert relay
communication between modules. These 3 wires run in parallel
from module to module. They connect to J9 on EMM and
AUX boards, and to J12 or J13 on SIOBs. A valid unit config-
uration must be in the Carrier Controller module for proper
LEN communication.
Carrier Comfort Network
All 30XV units can be connected to the CCN, if desired. The
communication bus wiring is RS-485 Communication Wiring,
CM or CMP rated consisting of a shielded, 3 conductor cable
with drain wire and is field supplied and installed. The system
elements are connected to the communication bus in a daisy
chain arrangement. The positive pin of each system element
communication connector must be wired to the positive pins of
the system elements on either side of it. The negative and signal
ground pins of each system element must also be wired in the
same manner. Wiring connections for CCN should be made at
TB3. See Fig. 22. For noise consideration, communication wir-
ing must be separate and not run in parallel with other wiring.
NOTE: Conductors and drain wire must be 20 AWG (American
Wire Gage) minimum stranded, tinned copper. Individual con-
ductors must be insulated with PVC (Polyvinyl Chloride), PVC/
nylon, vinyl, Teflon
1
, or polyethylene. An aluminum/polyester
100% foil shield and an outer jacket of PVC, PVC/nylon,
chrome vinyl, or Teflon with a minimum operating temperature
range of –20°C to 60°C is required. High temperature applica-
tions may require a higher temperature range. Plenum applica-
tions will require plenum rated cable. Cable voltage require-
ments must match the application.
1. Teflon is a registered trademark of DuPont.
19
I/O POINT
INPUT/OUTPUT
NAME
TYPE
AI-01
5/10K Thermistor
AI-02
10K Thermistor
AI-03
5/10K Thermistor
AI-04
5/10K Thermistor
AI-06
0-5V
AI-07
0-5V
AO-01
0-10 Vdc
DI-01
DI-02
DI-03
DI-04
DI-05
DI-06
DI-07
DI-08
DI-09
DO-01
Triac
DO-02
Triac
DO-09
Relay
DO-10
Relay
®
Interface

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents