Honeywell NOTIFIER NFXI-ASD11 Wiring Diagram page 9

Fire alarm aspiration sensing technolog y
Hide thumbs Also See for NOTIFIER NFXI-ASD11:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
PREALARM
8
4
4
10
7
3
3
9
6
2
2
8
1
1
5
Table 5: Front Panel Buttons
7
4
BUTTON
3
RESET
6
2
5
SMOKE
1
LEVEL 2
4
INITIALIZATION
3
DISABLE
POWER
2
FAULT
SMOKE
1
LEVEL 1
TEST
FAULT
COMBINATIONS
RESET + DISABLE
RESET + TEST
RESET + TEST + DISABLE
Password Sequence to Enter Maintenance Mode
Press and hold RESET; Left flow indicator will turn yellow, then
green.
Release RESET and FAULT indicator will switch on green. The
left flow indicator will blink green indicating the device is ready for
the first digit.
Press DISABLE to increment the LEDs 1...9; press TEST to select
a digit.
The flashing airflow segment will turn solid green and the next
segment will begin to flash indicating set the next digit. When the
4th digit is selected, all 4 airflow segments are turned off. If the
password is accepted the FAULT indicator will remain green and
the unit enters Maintenance mode. If the password is incorrect
the FAULT indicator flashes yellow and the unit remains in Normal
mode. The Default password in 3111.
If no button is pressed for 10s during the password sequence, the
unit returns to Normal mode.
Exit from Maintenance Mode
To exit from the Maintenance mode, press the three front panel
user interface buttons TEST, RESET and DISABLE simultaneously
for 2 seconds. Alternatively, reset the unit using the Remote Input
(when set to default value) or power the device off and on again.
If there is no activity in Maintenance mode for 5 minutes (default),
the FAULT indicator blinks green for 15s and then the unit
automatically returns to the Normal state.
TESTING
Note that the sensor LEDs, which are under the control of the CIE
(Fire Panel), must be turned on to activate the front panel alarm
indicators.
Magnet Test
The alarm signalling can be tested for functionality by placing a
test magnet in the position shown in Figure 9 (displayed earlier in
the guide). This method does not test the air flow in the pipe-work.
Smoke Testing
The system alarm response can be tested for functionality
using smoke. The choice of smoke source is dependant on the
installation but in all cases the smoke must be present for the
duration of the test. Smoke pellets or matches can be used close
to the sampling point to introduce smoke particulates into the
N200-102-00
10
9
SMOKE
8
LEVEL 2
7
INITIALIZATION
NORMAL Mode
When pressed for 2 s, starts PASSWORD
6
POWER
PROCEDURE to enter Maintenance
FAULT
5
mode.
4
3
Used to increment Password digits in
2
PASSWORD PROCEDURE
SMOKE
1
LEVEL 2
INITIALIZATION
Used to confirm password in PASSWORD
POWER
FAULT
PROCEDURE. Default Password = 3111
When pressed for 2 s, shows fan speed
(on smoke level scales) for a preset time.
No action
No action
MAINTENANCE Mode
When pressed for 2 s latched alarms, faults and
sounders (relays) are reset. Alarm controlled by panel. If
alarm persists, set again immediately after the reset
In DISABLE Mode, if pressed for 2 s unit will exit from
DISABLE Mode (but remains in MAINTENANCE Mode)
When pressed for 2 s, device enters DISABLE Mode for
60 minutes (default). Alarm and fault relays reset .
Smoke sensors continue to report alarm and their faults
to the panel.
(To exit DISABLE Mode see RESET)
When pressed for 2 s and released, both sensor will
simulate alarm
When pressed for 4 s and released, sensor #1 will
simulate alarm
When pressed for 6 s and released, sensor #2 will
simulate alarm
Warning: Outputs will be activated by test
When pressed for 2 s, shows fan speed (on smoke level
scales) for preset time.
When pressed for 2 s, turns off sounders
When pressed for 2 s, unit exits from MAINTENANCE
Mode
system. It is recommended that smoke with a particulate life cycle
of greater than 120s should be used – standard aerosol sprays for
point detector testing do not work well on aspirated systems.
Fault Testing
Simulate a fault on the detector (for example, block the outlet pipe)
and check that a fault is signalled on both the front panel of the unit
and at the CIE (Fire Panel).
SERVICE
Isolate the aspirating detector from the fire alarm system to prevent
any unwanted alarms when opening the front door of the unit.
Make sure all power is removed from the system before removing
any covers.
Service Mode
Opening the cabinet door during normal operation will cause the
unit to enter Service Mode. The FILTER LEDs will blink, the unit will
switch off power to the fans and stops communicating with the fire
panel (the smoke sensors continue to communicate with the panel).
When the cabinet door is closed, the unit restarts automatically.
Filters
Periodic cleaning or replacement of the filters will be required.
The filters are located inside the cabinet at the top of the unit (see
Figure 9 displayed earlier in the guide) and are removed as shown
in the sequence below:
1
F i lters
Either replace the filter assembly or carefully brush off the accumulated du
9
Refit the filter, close and secure the cabinet door. The unit will initialise and
WARNING
2
FOAM GASKET
I56-3947-202