Optional Accessories: A492 - Water Leackage Detector + Additional Detector; Optional Accessories: A511 - Smoke Detectors; Optional Accessories: A512 - Fire Detectors - Mitsubishi Electric t-NEXT DF DX 011 P1 S Manual

Air conditioners for it cooling with dual fluid system.to be matched with remote air-cooled condenser.
Table of Contents

Advertisement

t-NEXT DF DX
OPTIONAL ACCESSORIES: A492 – WATER LEACKAGE DETECTOR + ADDITIONAL DETECTOR

OPTIONAL ACCESSORIES: A511 - SMOKE DETECTORS

OPTIONAL ACCESSORIES: A512 – FIRE DETECTORS
T_tNEXTDFDX_0719_EN
The system includes an electronic relay installed in the electrical panel of the indoor machine and 2
water detectors to be connected in series.
The electrical connections for the probe and the alarm contact are present in the indoor machine's
terminal board.
The sensors are supplied to be connected and installed at customer care.
Is possible to install one or both of the following sensors. Sensors are supplied in mounting kit.
Installation within the room at customer care.
A511 - SMOKE DETECTOR
The device in supplied in mounting kit.
The optical smoke detector senses the presence of combustion by-products (visible smoke) and
activates an alarm.
The operating principle is based on the light scattering technique (Tyndall effect).
The device is in conformity to EN 54-7 standard.
Technical features:
Material
ABS
Power supply
12...28 Vdc
Normal current
50μA 24 Vdc
Alarm current
25mA 24 Vdc
LED visibility
360° (double led)
Storage temperature
-10...+70°C
Operating temperature
-10...+70°C
Max. speed air
0.2 m/s
Supplied with unit to be connected and installed at customer care close to the unit.
A512 - FIRE DETECTOR
The device in supplied in mounting kit.
The fire detector has been designed to identify temperatures at which fires may start. When the
temperature exceeds the set threshold or when there is a rapid variation in temperature, the relay is
activated to signal an alarm.
The device is in conformity to EN 54-5 standard.
Technical features:
Material
ABS
Power supply
12...28 Vdc
Normal current
50μA 24 Vdc
Alarm current
25mA 24 Vdc
LED visibility
360° (double LED)
Storage temperature
-10...+70°C
Operating temperature
-10...+70°C
Relative humidity
<93% non-condensing
Supplied with unit to be connected and installed at customer care close to the unit.
37
Relative humidity
<93% not-condensing
Index of protection
IP 20
Testing by magnet
Yes
Relay
max. 1A 30Vdc
Signal repeater
14mA 24 Vdc
Covered area
40m
max.
2
Shielded connection
Min. 0.5 mm
cable
Colour
White
Index of protection
IP 20
Testing by magnet
Yes
Relay
max. 1A 30Vdc
Signal repeater
14mA - 24 Vdc
Alarm temperature
62°C
threshold
Covered area
40m
2
max.
Shielded connection
Min. 0.5 mm
cable
Colour
White
2
2
MEHITS S.p.A.
DATA BOOK