ELECTRICAL DATA

VERSION (1)
MODEL
SIZE
Power supply
Maximum current input (FLA)
VERSION (1)
MODEL
SIZE
Power supply
Maximum current input (FLA)
VERSION (1)
MODEL
SIZE
Power supply
Maximum current input (FLA)
VERSION (1)
MODEL
SIZE
Power supply
Maximum current input (FLA)
1.
U = Under, downflow / O = Over, upflow
WARNING:
The electric data indicated refer only to the indoor unit.
Optional accessory electric data are included within the dedicated chapters and must be added.
Please refer to ELCA WORLD selection program to calculate the electrical data of the air conditioner according to the requested optional
accessories.
The remote air-cooled condenser is not included because it has independent power supply.
T_tNEXTDFDX_0719_EN
Electrical data of the system at full load working conditions.
U / O
011 P1 S
E1
V/ph/Hz
400/3+N/50
A
7,65
U / O
026 P1 S
E3
V/ph/Hz
400/3+N/50
A
20,4
U / O
039 P2 D
E5
V/ph/Hz
400/3+N/50
A
26,2
U / O
082 P2 D
E7
V/ph/Hz
400/3+N/50
A
58,9
28
U / O
U / O
014 P1 S
016 P1 S
E2
E2
400/3+N/50
400/3+N/50
10,0
11,5
U / O
U / O
032 P1 S
037 P1 S
E4
E4
400/3+N/50
400/3+N/50
22,4
25,8
U / O
U / O
048 P2 D
055 P2 D
E5
E6
400/3+N/50
400/3+N/50
34,4
40,8
U / O
U / O
092 P2 D
102 P2 D
E8
E8
400/3+N/50
400/3+N/50
70,9
76,9
U / O
U / O
020 P1 S
022 P1 S
E3
E3
400/3+N/50
400/3+N/50
15,2
19,2
U / O
U / O
041 P1 S
045 P1 S
E4
E4
400/3+N/50
400/3+N/50
29,4
35,4
U / O
U / O
062 P2 D
075 P2 D
E6
E7
400/3+N/50
400/3+N/50
44,8
52,1
U
U
117 P4 D
146 P4 D
E9
E9
400/3+N/50
400/3+N/50
86,1
113,0