Mitsubishi Electric t-NEXT DF DX 011 P1 S Manual page 15

Air conditioners for it cooling with dual fluid system.to be matched with remote air-cooled condenser.
Table of Contents

Advertisement

t-NEXT DF DX
TECHNICAL DATA
VERSION (1)
MODEL
SIZE
COOLING CAPACITY (2)
Total
Sensible
SHR (3)
Total power input (Comp. + Fans)
"EC" SUPPLY FANS
Air flow
Nominal external static pressure
Maximum external static pressure
Fans power input (4)
ON/OFF COMPRESSORS
Compressors number
Capacity steps
Compressors power input
AIR FILTERS
Filter area
Efficiency (ISO EN 16890)
REFRIGERANT CIRCUITS
POWER SUPPLY
ENERGY EFFICIENCY INDEX (2) (5)
EER Energy Efficiency Ratio
DIMENSIONS
Length
Width
Height
NET WEIGHT OVER
NET WEIGHT UNDER
REFRIGERANT CONNECTIONS
Gas delivery
Liquid return
HYDRAULIC CONNECTIONS
CONDENSATE DISCHARGE
Rubber pipe – internal diameter
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1.
U = Under, downflow / O = Over, upflow
2.
Gross value. Characteristics referred to entering air at 26°C-40%RH; condensing temperature 45°C. ESP=20Pa.
3.
SHR = Sensible cooling capacity / Total cooling capacity.
4.
Corresponding to the nominal external static pressure
5.
The Energy Efficiency Index does not consider the remote air-cooled condenser.
The units highlighted in this publication contain <HFC R410A [GWP
T_tNEXTDFDX_0719_EN
U / O
026 P1 S
E3
kW
26,2
kW
25,3
0,97
kW
6,74
n.
1
m³/h
6400
Pa
20
Pa
665
kW
1,19
scroll
n.
1
n.
1
kW
5,55
n.
2
m
2
1,24
COARSE
60%
n.
1
V/Ph/Hz
400/3+N/50
kW/kW
3,89
mm
1085
mm
775
mm
1925
kg
338
kg
358
ODS Ø
22
ODS Ø
16
Ø mm
19
2088]> fluorinated greenhouse gas
100
15
U / O
U / O
032 P1 S
037 P1 S
E4
E4
32,5
37,6
32,5
37,6
1
1
7,62
9,25
1
1
8700
10000
20
20
512
175
1,42
2,1
scroll
scroll
1
1
1
1
6,2
7,16
2
2
2,07
2,07
60%
60%
1
1
400/3+N/50
400/3+N/50
4,27
4,06
1305
1305
930
930
1980
1980
462
467
472
477
22
22
16
16
19
19
U / O
U / O
041 P1 S
045 P1 S
E4
E4
41,4
45,4
41,2
43,4
1
0,96
10,2
11,2
1
1
10800
10800
20
20
332
332
2,08
2,08
scroll
scroll
1
1
1
1
8,1
9,13
2
2
2,07
2,07
60%
60%
1
1
400/3+N/50
400/3+N/50
4,06
4,05
1305
1305
930
930
1980
1980
479
487
489
497
22
22
22
22
19
19
MEHITS S.p.A.