Gb Continuity - Siemens FC121-ZA Technical Manual

Fire control panel
Hide thumbs Also See for FC121-ZA:
Table of Contents

Advertisement

4.3.3
24
Smart Infrastructure

GB continuity

The GB continuity line allows a mixture of MCPs and detectors within the same zone.
In addition this mode supports a reliable operation, even though one or more detectors
are removed from its base. The CIE detect the removed detector and report a zone fault.
Technical:
-
Special detector bases equipped with a diode (1N5819):
DB110D part number S54372-F6-A1 or DB110RD part number S54372-F8-A1
-
MCPs require a Z-diode for direct alarming (AVC).
-
Siemens detectors 110-series or detectors with an alarm resistor are required for
delayed alarming (AVC, V1 / V2).
-
Each line must be terminated with EOL element Capacitor 10 µF.
-
Limitation: Max. 18 detectors per line is allowed due to voltage drop on the detector
base.
-
MCPs have no limitation and can be installed to reach the maximum of 32 devices.
Programming:
Configure g Zone g Zone 1 – n g Mode g GB continuity
-
Configure g Zone g Zone 1 – n g AVC g Via AVC timer MCP direct
-
NOTICE
See details of the specification in chapter 3.3.1.
Zone mode 'GB continuity' does NOT comply with EN 54-13.
Behavior of MCP in zone coincidence with function 'direct alarming' is not supported.
EOL
+
+
+
ZONE1
A6V10393190_h_en_--
2019-09-01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc122-zaFc123-zaFc124-za

Table of Contents