Reconfiguration Of A Device Operated In Sil Mode - Siemens SITRANS F Additional Operating Instructions

Vortex flowmeters, functional safety
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

SITRANS FX330
Setting of the SIL jumper
• Remove the display while device is powered (for details refer to [N1], chapter "Turning the
display").
• Set the jumper to SIL position as shown in the figures below.
• Reattach the display.
Figure 3-1: Jumper position
1 Non-SIL position
2 SIL position
After setting the jumper to the SIL position, the flowmeter will perform an automatic reboot and
start operation in SIL mode. The operation in SIL mode is indicated by a small SIL logo.
Figure 3-2: Indication of SIL mode
1 SIL logo for indication of SIL mode

3.2 Reconfiguration of a device operated in SIL mode

The device must be set to non-SIL mode first, before any parameter can be changed, as changing
of parameters is prohibited in SIL mode.
Follow the steps shown in the next chapter and then reconfigure the device.