Siemens SITRANS F Additional Operating Instructions page 21

Vortex flowmeters, functional safety
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

SITRANS FX330
• Integrate a current meter into the current loop.
• Disconnect the 3-pole plug and connect a frequency generator as illustrated below.
The 2-pole and 5-pole plugs must remain connected!
The 2-pole and 5-pole plugs must remain connected!
The 2-pole and 5-pole plugs must remain connected!
The 2-pole and 5-pole plugs must remain connected!
Figure 4-2: Connection of frequency generator
1 Frequency f1
2 Grounding
3 Frequency f2, phase-shifted by 180° compared to f1
• Set start frequencies f1 and f2 to almost 0 Hz.
• Connect the flowmeter with the power supply.
• Boot the device.
• Confirm request "Press key for verification" by pressing any key.
• Login as "Expert".
• After reboot of the device activate proof test as follows:
Menu/display
A Quick Setup
C Setup
C6 Device
C6.8 Proof Test
"Unsaved
parameters will be
lost!"
"Run Proof Test?"
If question "Confirm start of proof test?" has been confirmed with "YES", the device is prepared
for proof test and displays "Proof Test is running...".
10/2017 - A5E40875009-AB EN
To do
Enter menu
Go to "C Setup"
Go to "C6 Device"
Go to "C6.8 Proof Test"
Enter "Proof Test"
Confirm warning with enter
Confirm start of proof test with "YES" or cancel with "NO"
www.siemens.com/flow
SERVICE
4
Keys
1 x →
2 x ↓
1 x →, 5 x ↓
1 x →, 6 x ↓
1 x →
1 x ^
YES / NO ^
21