No internal fuse
External preliminary protection with max. C 10 A circuit breaker in the supply line required
under all circumstances.
Operational data
PID control:
Minimum switch on/off time
Minimum period time
Setpoint setting range
Factory setting comfort setpoint
Factory setting for energy saving mode
Resolution of
settings and
displays
Electrical connections
Connections terminals (via baseplate)
For solid wires
For stranded wires
Environmental conditions
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Storage
Climatic conditions
Temperature
Humidity
Standards, directives and approvals
EU conformity (CE)
RCM conformity
Safety class
Siemens
Building Technologies
WARNING
Temperature
setpoint
Display of actual
temperature value
Slow
4 min
12 min
5...30 °C (Comfort mode)
5...30 °C (Energy saving mode)
5 °C (Frost Protection, fixed value)
20 °C
10 °C
0.5 °C
0.5 °C
Screw terminals
2 x 1.5 mm
2
1 x 2.5 mm
(min. 0.5 mm
2
IEC 60721-3-3
Class 3K5
0...+40 °C
<90% r.h.
IEC 60721-3-2
Class 2K3
-25...+60 °C
<95% r.h.
Class 2M2
IEC 60721-3-1
Class 1K3
-10...+60 °C
<90% r.h.
A6V101123363 *)
A6V11161600 *)
II as per EN 60730-1
Datasheet
Fast
2 min
6 min
)
2
11
A6V10954415_en--_e
2018-11-20