Filters; Dimensions (Upflow Configuration Shown); Side Return Cutout Markings; Cabinet And Duct Dimensions - Mm9E - York MM9E Series Installation Manual

Single stage manufactured housing or modular home gas furnaces
Table of Contents

Advertisement

FIGURE 9: Dimensions (Upflow Configuration Shown)
Table 2: Cabinet and Duct Dimensions - MM9E
Nominal
BTUH (kW)
3
Input
CFM (m
60 (17.6)
1200 (34.0)
80 (23.4)
1200 (34.0)
80 (23.4)
1600 (45.3)
80 (23.4)
2000 (56.6)
100 (29.3)
1600 (45.3)
SECTION III: FILTERS
FILTER INSTALLATION
All applications require the use of a field installed filter. All filters and
mounting provision must be field supplied.
Filters must be installed external to the furnace cabinet. DO NOT
attempt to install filters inside the furnace.
NOTICE
Single side return above 1800 CFM is approved as long as the filter
velocity does not exceed filter manufacturer's recommendation and
a transition is used to allow use on a 20x25 filter.
Table 3: Recommended Filter Sizes (High Velocity 600 FPM)
CFM
Cabinet
(m³/min)
Size
1200 (34.0)
B
1600 (45.3)
C
2000 (56.6)
C
1. Air velocity through throwaway type filters must not exceed 300 ft per minute
(91.4 m/min). All velocities over this require the use of high velocity filters.
2. Do not exceed 1800 CFM using a single side return and a 16 x 25 filter. For
CFM greater than 1800, you can use two side returns or one side and the
bottom or one side return with a transition to allow use of a 20 x 25 filter.
Johnson Controls Ducted Systems
Cabinet
Size
/min)
A (in.)
B
17 1/2
B
17 1/2
C
21
C
21
C
21
Side
Bottom
(in.)
(in.)
16 x 25
16 x 25
16 x 25
20 x 25
(2) 16 x 25
20 x 25
Cabinet Dimensions (Illustrated in Figure 9)
A (cm)
B (in.)
B (cm)
44.4
16 3/8
41.6
44.4
16 3/8
41.6
53.3
19 7/8
50.5
53.3
19 7/8
50.5
53.3
19 7/8
50.5
SIDE RETURN - UPFLOW ONLY
Locate the L shaped corner locators. These indicate the size of the cut-
out to be made in the furnace side panel. Refer to Figure 10.
FIGURE 10: Side Return Cutout Markings
Install the side filter rack following the instructions provided with that
accessory. If a filter(s) is provided at another location in the return air
system, the ductwork may be directly attached to the furnace side
panel.
IMPORTANT: Some accessories such as electronic air cleaners
and pleated media may require a larger side opening. Follow the
instructions supplied with that accessory for side opening require-
ments. Do not cut the opening larger than the dimensions for the
Optional Return Air Cutout shown in Figure 9.
5715184-BIM-A-0519
Approximate
Operating Weights
C (in.)
C (cm)
lbs
13 1/4
33.7
122
14 3/4
37.5
126
16 1/2
41.9
136
16 1/2
41.9
139
18 1/4
46.4
142
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

M9e080b12Mm9e080c16Mm9e080c20Mm9e060b12Mm9e100c16

Table of Contents