Checking Outputs (Relay Test) - Viessmann Vitodens 200-W B2HA 112 Installation Instructions Manual

Wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HA 112:
Table of Contents

Advertisement

Scanning Options

Checking Outputs (Relay Test)

1. Press OK and
simultaneously for approximately
4 seconds.
2. "Actuator test"
The following relay outputs can be controlled subject to system design:
Display
All actuators
Base load
Full load
Output, internal
Output 21/28
Outp. int. exten. H1
EA1 output 1
14
Explanation
Off
All actuators are off.
On
Burner operated at minimum output; circulation pump sÖ is started.
On
Burner operated at maximum output; circulation pump sÖ is started.
On
Output sÖ active.
On
Output sA active.
On
Output 28/20 active.
On
Contact P - S at plug aBJ of extension EA1 closed.