Solenoid Current Monitoring; Propxd Parameterizing Software - Parker D41FE Operation Manual

Pilot operated proportional directional control valve
Table of Contents

Advertisement

Operation Manual

Solenoid Current Monitoring

If the actuator current time interval exceeds 10
seconds, the actuator is switched off to prevent
overheating. For normal operating conditions this
state will not reached, but it may occur with a con-
taminated sluggish valve.
In this case the reason for the contamination
should be repaired (hydraulic fluid exchange,
filtration review, valve flushing).
The overcurrent shutoff condition may be resetted
by the actions below:
Code 0: Temporary disconnection of the supply
voltage.
Code 5: Temporary disconnection of the enable
signal.
Code 7: Temporary disconnection of the enable
signal.
The shutoff of the VCD actuator due to over-
load will be signaled via the diagnostics
output.

ProPxD parameterizing software

The ProPxD software permits comfortable param-
eter setting for the module electronic. Via the clearly
arranged entry mask the parameters can be noticed
and modified. Storage of complete parameter sets
is possible as well as printout or record as a text
file for further documentation.
See www.parker.com/isde section "Support" for
free software download. Please check periodical
for updates.
Hardware requirements
• PC with operating system from Windows
upwards
• Interface RS232
• display resolution min. 800 x 600
• connection cable between PC and electronic
module
• storage requirement approx. 40 MB
If your PC has no serial interface according
to RS232 standard you require in addition an
USB-RS232 adapter.
D_1FE 5715-688 UK CM 18.01.2019
Pilot Operated Proportional DC Valve
Series D*1FE
Cable Specification
Attention! The valve electronic provides no
USB interface, but can only be parametrized
via an RS232 - connection. Therefore the
usage of USB standard cables is not allowed
and may result in damaging of valve resp. PC.
Parametrizing
Ordering code: 40982923
Parametering interface
Plug for
parametering interface
XP
®
The cover plug has to be re-installed after
completion of the parametrizing work.
13