Maintenance; Zero Reset - Siemens QBM97 Series User Manual

Modbus air pressure sensor with i/o extension
Table of Contents

Advertisement

Maintenance

4

Zero reset

4 Maintenance
4.1 Zero reset
Perform the zero reset without tubes
Blue
10...20 s
20 | 22
Siemens
Building Technologies
NOTICE
Use cases of the zero reset
As the allowed mounting position is vertical only (see "Mounting [➙ 4]") the
sensor does not have to be recalibrated during commissioning in the case of
normal pressure measurement.
Only in case of relative pressure measurement (pressure nipple "-" connected
to ambient atmosphere) a zero point calibration is recommended during
commissioning.
Afterwards connect the tubes again
A6V11478123_en_a
2019-02-01

Advertisement

Table of Contents
loading

Table of Contents