16.5 Hochiki Multi-Sensor Support
•
The Hochiki Multi-Sensor is supported as detailed below from panel software version 824 onwards.
Previously, from version 698, the multi-sensor was partially supported – operating as an optical smoke
device becoming more sensitive with temperatures above 40 °C.
•
Where the control panel is in normal operation or sensitivity day mode is invoked, the multi-sensor
mode and threshold parameters can be modified according to the specific site requirements. This
allows a different mode of operation at different times of the day (see Section 11.3 Sensitivity Mode).
For each multi-sensor address, in the edit device menu, choose to 'edit thresholds'. Firstly, the mode
of operation will be presented. Select 0 for multi-mode, 1 for optical-smoke only mode or 2 for heat
only mode. Normal threshold set-up will follow. These settings will take effect on a device by device
basis throughout the day mode period (where sensitivity mode is programmed).
•
Where night mode is invoked (as part of sensitivity day mode), the device operates in the multi-sensor
mode providing the control panel with an analogue value representing a combination of the smoke
and heat elements of the sensor. The pre-alarm threshold is fixed at 45 and the full-alarm threshold at
55.
16.6 System Sensor/ Morley-IAS Multi-Sensor & Laser Support
16.6.1 System Sensor/ M-IAS Multi & Laser Diagnostics
•
When viewing the device from the user menus, the meaning of the analogue value is as follows:
Value displayed
0
1
2
3
4
4 or 7
5
10
15
20
29 multi / 32 laser
50 multi / 50 laser
64 multi / 57 laser
79 multi / 64 laser
93 multi / 71 laser
107 multi / 79 laser
121 multi / 86 laser
- / 93 laser
- / 100 laser
- / 107 laser
Page 58
Multi
No device
Mid-range invalid
Mid-range invalid
Mid-range invalid
Mid-range invalid
Out of range
Low chamber trouble
Maintenance alert
Maintenance urgent
initialising
Normal
Level 1 alarm
Level 2 alarm
Level 3 alarm
Level 4 alarm
Level 5 alarm
Level 6 alarm (HEAT)
-
-
-
System Sensor Multi-sensor & Laser Diagnostics
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
laser
No device
Mid-range invalid
Mid-range invalid
Mid-range invalid
Mid-range invalid
Out of range
Drift alert 0.3%
Maintenance alert
Drift alert 0.6%
Initialising
Normal
Level 1 alarm
Level 2 alarm
Level 3 alarm
Level 4 alarm
Level 5 alarm
Level 6 alarm
Level 7 alarm
Level 8 alarm
Level 9 alarm