16.5 Hochiki Multi-Sensor Support

The Hochiki Multi-Sensor is supported as detailed below from panel software version 824 onwards.
Previously, from version 698, the multi-sensor was partially supported – operating as an optical smoke
device becoming more sensitive with temperatures above 40 °C.
Where the control panel is in normal operation or sensitivity day mode is invoked, the multi-sensor
mode and threshold parameters can be modified according to the specific site requirements. This
allows a different mode of operation at different times of the day (see Section 11.3 Sensitivity Mode).
For each multi-sensor address, in the edit device menu, choose to 'edit thresholds'. Firstly, the mode
of operation will be presented. Select 0 for multi-mode, 1 for optical-smoke only mode or 2 for heat
only mode. Normal threshold set-up will follow. These settings will take effect on a device by device
basis throughout the day mode period (where sensitivity mode is programmed).
Where night mode is invoked (as part of sensitivity day mode), the device operates in the multi-sensor
mode providing the control panel with an analogue value representing a combination of the smoke
and heat elements of the sensor. The pre-alarm threshold is fixed at 45 and the full-alarm threshold at
55.
16.6 System Sensor/ Morley-IAS Multi-Sensor & Laser Support
16.6.1 System Sensor/ M-IAS Multi & Laser Diagnostics
When viewing the device from the user menus, the meaning of the analogue value is as follows:
Value displayed
0
1
2
3
4
4 or 7
5
10
15
20
29 multi / 32 laser
50 multi / 50 laser
64 multi / 57 laser
79 multi / 64 laser
93 multi / 71 laser
107 multi / 79 laser
121 multi / 86 laser
- / 93 laser
- / 100 laser
- / 107 laser
Page 58
Multi
No device
Mid-range invalid
Mid-range invalid
Mid-range invalid
Mid-range invalid
Out of range
Low chamber trouble
Maintenance alert
Maintenance urgent
initialising
Normal
Level 1 alarm
Level 2 alarm
Level 3 alarm
Level 4 alarm
Level 5 alarm
Level 6 alarm (HEAT)
-
-
-
System Sensor Multi-sensor & Laser Diagnostics
Document No. 996-175-000-1, Revision 01
ZX Fire Alarm Control Panels
laser
No device
Mid-range invalid
Mid-range invalid
Mid-range invalid
Mid-range invalid
Out of range
Drift alert 0.3%
Maintenance alert
Drift alert 0.6%
Initialising
Normal
Level 1 alarm
Level 2 alarm
Level 3 alarm
Level 4 alarm
Level 5 alarm
Level 6 alarm
Level 7 alarm
Level 8 alarm
Level 9 alarm
Commissioning Manual