13 Hand-over to the user
2 Press
.
3 Press
to interrupt the program.
4 Select OK and press
.
Result: The underfloor heating screed dryout program is stopped.
When the program is stopped due to an error, an operation switch-
off, or a power failure, you can read out the underfloor heating
screed dryout status.
5 Go to [A.7.2]:
> Installer settings > Commissioning > UFH
screed dryout > Dryout status > Stopped at and followed by the
last executed step.
6 Modify and restart the execution of the program.
12.4.5

To perform a gas pressure test

1 Connect a suitable gauge on the gas valve. Static pressure
MUST be 20 mbar.
2 Select test program " ". See
the gas boiler" on
page 82. Static pressure MUST be 20 mbar
(+ or – 1  mbar). If the working pressure is <19  mbar, the gas
boiler output will be reduced and the correct combustion
reading may NOT be obtained. Do NOT adjust the air and/or
gas ratio. To obtain sufficient working pressure, gas supply
MUST be correct.
INFORMATION
Make sure the working inlet pressure does NOT interfere
with other gas appliances installed.
12.4.6

To perform a test run on the gas boiler

The gas boiler has a test run function. Activating this function results
in the activation of the gas boiler (pump starts and fan starts with a
fixed speed), without the control functions being actuated. The safety
functions remain active. The test run can be stopped by pressing
and
simultaneously or will end automatically after 10 minutes. To
perform a test run, switch off the system with the user interface.
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are
turned OFF.
There may be no error on the gas boiler or the heat pump module.
During a gas boiler test run, "busy" will be displayed on the user
interface.
Installer reference guide
82
"12.4.6  To perform a test run on
Program
Button combination
Burner ON at
minimum power
Burner ON, maximum
and
space heating power
setting
Burner ON, maximum
and
domestic hot water
setting
Stop test program
NOTICE
If an 81‑04 error occurs, then do NOT perform a test run
on the gas boiler.
13
Hand-over to the user
Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:
▪ Fill in the installer setting table (in the operation manual) with the
actual settings.
▪ Make sure that the user has the printed documentation and ask
him/her to keep it for future reference. Inform the user that he can
find the complete documentation at the URL mentioned earlier in
this manual.
▪ Explain the user how to properly operate the system and what to
do in case of problems.
▪ Show the user what to do for the maintenance of the unit.
▪ Explain the user about energy saving tips as described in the
operation manual.
14

Maintenance and service

Especially for UK:
After servicing, complete the relevant Service Interval Record
section of the Benchmark Checklist located on the backpages of this
document.
NOTICE
Maintenance MUST be done by an authorized installer or
service agent.
We recommend performing maintenance at least once a
year. However, applicable legislation might require shorter
maintenance intervals.
14.1
Overview: Maintenance and
service
This chapter contains information about:
▪ The yearly maintenance of the outdoor unit
▪ Cleaning the gas boiler
14.2

Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
Daikin Altherma Hybrid hydrosplit heat pump
Display
and
(1×)
(2×)
and
Actual situation
EJHA04AAV3 + EHY2KOMB28+32AA
4P531180-1 – 2018.06