Technical specifications
Detailed technical data
Table 5- 2
Technical specifications of motor reactors 380 V – 480 V 3 AC, part 1
Order number
Suitable for Power Module
Rated current
Power loss
- at 50 Hz
- at 150 Hz
Connections
- to the Power Module
- load
- PE
Max. permissible cable
length between motor reactor
and motor
Degree of protection
Dimensions
Width
Height
Depth
Weight
Table 5- 3
Technical specifications of motor reactors 380 V – 480 V 3 AC, part 2
Order number
Suitable for Power Module
Rated current
Power loss
- at 50 Hz
- at 150 Hz
Connections
- to the Power Module
- load
- PE
Max. permissible cable
length between motor reactor
and motor
Degree of protection
Dimensions
Width
Height
Depth
Weight
18
6SL3000-
2BE32-1AA0
6SL3310-
1GE32-1AAx
A
210
kW
0.436
kW
0.486
M10
M10
M8
m
IP00
mm
300
mm
285
mm
257
kg
66
6SL3000-
2BE35-0AA0
6SL3310-
1GE35-0AAx
A
490
kW
0.448
kW
0.5
M12
M12
M8
m
IP00
mm
300
mm
365
mm
277
kg
100
2BE32-6AA0
2BE33-2AA0
1GE32-6AAx
1GE33-1AAx
260
310
0.454
0.422
0.5
0.47
M10
M10
M10
M10
M8
M8
300 (shielded)
450 (unshielded)
IP00
IP00
300
300
315
285
277
257
66
2AE36-1AA0
2AE38-4AA0
1GE36-1AAx
1GE37-5AAx
605
840
0.798
0.75
0.9
0.84
M12
M12
M12
M12
M10
M10
300 (shielded)
450 (unshielded)
IP00
IP00
410
410
392
392
292
292
130
140
Operating Instructions, 03/2012, A5E00409660A
2BE33-8AA0
1GE33-8AAx
380
0.447
0.5
M10
M10
M8
IP00
300
285
277
66
73
2AE38-4AA0
1GE38-4AAx
840
0.834
0.943
M12
M12
M10
IP00
410
392
292
140