Maintenance; Burner Start-Up Cycle - Riello Gulliver RG0.3 Installation, Use And Maintenance Instructions

Oil burner
Hide thumbs Also See for Gulliver RG0.3:
Table of Contents

Advertisement

Available languages

Available languages

4.2 BURNER START-UP CYCLE

Normal
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
A
Lock out is indicated by a lamp on the control box (3, fig. 1, page 1).

5. MAINTENANCE

Burner requires a periodic maintenance carried out by a qualified and authorized technicians.
Maintenance is essential for the reliability of the burner, avoiding the excessive consumption of fuel and
consequent pollution.
Before carrying out any cleaning or control always first switch off the electrical supply to the
burner acting on the main switch of the system.
Check that there are not obstructions or dents in the supply or return oil pipes.
Clean the filter in the oil suction line and in the pump.
Check for correct fuel consumption.
Replace the nozzle.
Clean the combustion head in the fuel exit area, on the diffuser disc.
Leave the burner working without interruptions for 10 min. and set rightly all the components stated in
this manual. Then carry out a combustion check verifying:
Smoke temperature at the chimney;
Content of CO
( % );
2
Content of CO (ppm);
Smoke value according to opacity smokes index according to Bacharach scale.
2301
~
12s
THE BASIC CHECKS ARE:
Lock-out due to failure to light
~
12s
8
GB
A
5 s
D5029

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents