Samsung AC026RN1DKG Service Manual page 156

System air conditioner single for europe (r32, heat pump)
Hide thumbs Also See for AC026RN1DKG:
Table of Contents

Advertisement

Troubleshooting
IPM over (Over Current) error (Error Code : E464)(cont.)
1. Did compressor wires assembled
in the appropriate color? (U:Red, V:Blue, W:Yellow) →
Check for disconnections of PCB and COMP.
2. Is the terminal in the compressor
wire housing firmly assembled?
3. Is there any fault of compressor wires
in disconnection or cutting?
Replace the PCB.
※ E46 Error-related, EMI / outdoor unit Main / Indoor unit Main PCB do not replace!
→ This error is related to the Inverter PCB. (Not related to the above PCB)
※ Ensure that the service valve is open!
→ When the service valve is closed, the defects may be caused by differential
pressure when starting the compressor.
4-44
Continue
Yes
Yes
1. Replace the compressor wire. → Power ON.
→ Check normal startup. → End the service.
No
2. Replace the compressor wire. → Power ON.
→ Check normal startup. → End the service.
3. Replace the compressor wire. → Power ON.
→ Check normal startup. → End the service.
Samsung Electronics