Samsung AC026RN1DKG Service Manual page 145

System air conditioner single for europe (r32, heat pump)
Hide thumbs Also See for AC026RN1DKG:
Table of Contents

Advertisement

Indoor/outdoor communication error (1 min.) (Error Code: E202) (cont.)
Continue
Yes
Check the communication circuit of the Main
PCB of the outdoor unit.
1. Is there a fault in communication IC?
2. Is there a fault in TVS-Diode?
Measuring
Communication IC Measuring Part
Part
(Circuit Diagram)
Location
Measuring
#5-GND, #6- Communication A, #7-
Point
Communication B, #8-Vcc
Communication IC Measuring (Port)
#6 - #5
#7 - #5
#8 - #5
TVS-Diode Measuring
Both ends of diode
Samsung Electronics
Example of Measuring
Communication IC
CommB(#7)
CommA(#6)
Vcc(#8)
Steady-state Measuring Value
COM 1(RED)
0.9kΩ ~ 1.2kΩ
0.9kΩ ~ 1.2kΩ
4.7Vdc ~ 5.3Vdc
Example of Measuring
TVS-Diode
GND(#5)
Remark
Measuring after separating the communicatio
connection
Steady-state Measuring Value
1kΩ or above