Event History - Honeywell Touchpoint 1 Technical Manual

Single channel gas detector controller
Table of Contents

Advertisement

8
Press OK.
The display then shows a 10 second countdown.
When the countdown is complete the display shows GOOD if the
span has succeeded.
If the span fails the display shows FAIL and returns to the
beginning of the span menu.
9
Press OK.
The display returns to the menu selection screen.
10
Press Cancel.
Returns controller to normal operation.

Event History

This menu is for the review the last 10 time and date action records for alarms, faults and
controller Power On/Off events.
1
Access the menu system and select the
Press Up or Down. The icon flashes.
2
Press OK.
The display shows a flashing A1 to
indicate Alarm 1 event history is initially
selected.
3
Select from:
A1- Alarm 1 (default)
A2- Alarm 2
F- Fault
On/Off- Power
Use the Up/Down buttons.
4
Press OK to access the selected history.
001 to 010 are shown on the display to indicate
the position in the series of records.
For example if A1 is selected by pressing OK the screen displays its ON record initially.
ON — indicates time/date the alarm activated.
By pressing Up/Down the OFF record is then displayed.
OFF — indicates the time/date when a latched alarm was accepted/reset, or the
time/date a non-latched alarm automatically reset.
010 indicates the last (10th) record.
TP1MAN Issue 3 Apr 06 (MAN0630)