Fire hazard due to overheating when the total length of the power cables is exceeded
Overheating of the line filter and fire can result when the total length of the motor cables is
exceeded.
• Ensure that the total length of the motor cables does not exceed 100 m.
NOTICE
Destruction or damage to additional loads as a result of undesirable line harmonics
Line harmonics can occur if line filters that differ from those listed in this manual are used.
These can disturb or damage other loads connected to the line supply.
• Only use line filters that are listed in this manual.
NOTICE
Destruction or damage to components by incorrectly connecting the line filter
When incorrectly connecting the line filter, these components can be destroyed or
damaged.
• Only connect the Line Module to the SINAMICS line filter via the associated line reactor.
• Connect additional loads upstream of the SINAMICS line filter (if required, via a
Note
Disconnect the line filter for a high-voltage test
If a high-voltage test is conducted with alternating voltage in the system, the existing line
filters must be disconnected in order to obtain accurate measurements.
The connection clip to the interference suppression capacitor in the Power Module must also
be removed for a high-voltage test with direct voltage.
Line filter
Operating Instructions, 04/2014, A5E00331460A
CAUTION
separate line filter).