Items Sold Separately; Installation Space; Installation Procedures - Mitsubishi Electric AE-200A Installation Manual

Air conditioning control system centralized controller
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

5-3. Items sold separately

Items sold separately
Electrical box
L-fittings
Mounting kit
DIN rail attachments
Mounting Attachment
Surface cover with USB port
External input/output adapter

5-4. Installation space

Leave a space around the AE-200/AE-50 as shown in the figure below.
30 (1-3/16)
30 (1-3/16)
Note
When installing two or more AE-200/AE-50 controllers side-by-side, leave a space of at least 30 mm (1-3/16 in) between
them.
When installing two or more AE-200/AE-50 controllers vertically, leave a space of at least 40 mm (1-37/64 in) between them.
For the installation space for installation method 4, refer to the separately-sold mounting kit's Installation Manual .

5-5. Installation procedures

Note
Connect the necessary cables and wires before installing AE-200/AE-50, referring to chapters 6 and 9.
Do not install the unit where the unit may continuously receive vibration. The continuous vibration may cause the connector
pins to disconnect.
Important
When routing the cable from above, let the cable hang loose behind the controller as shown in the figure below to prevent
water from running down the cable into the connectors.
Good example
WT07935X04
Model name
PAC-YG84UTB-J
PAC-YG86TK-J
PAC-YG82TB-J
PAC-YG72CWL-J
PAC-YG10HA-E
Unit: mm (in)
30 (1-3/16)
30 (1-3/16)
40 (1-37/64)
40 (1-37/64)
Bad example
14
Remarks
Required only for installation method 2
Required only for installation method 4
Required only for installation method 5
Required when using a cover with USB port
Required when using the external input/output function