Honeywell CENTRA LINE LION CLLIONLC01 Installation & Commissioning Instructions page 63

Table of Contents

Advertisement

LION System
Terminals
COM
71
A
COM
72
B
24
73
V~
24
74
V~0
BINARY
ANALOG
INPUTS
INPUTS
B7
B8 B9
AI5 AI6 AI7 AI8
B10 B11 B12
7
8 9 10 11 12
17 18 19 20
B1
B2
B3
B4
B5
B6
AI1 AI2
AI2 AI3 AI4
3
5
6
13 14
14 15 16
1
2
4
Fig. 87
Terminal assignment and internal connections of mixed Panel Bus I/O module terminals
Terminal
Signal
LED
71, 75
COM a
status
72, 76
COM b
status
73, 77
24 V~
power
74, 78
24 V~0
power
1...7
BI1...7
1...7
8...12
BI8...12
24...28
13...20
AI1...8
41, 42
GND
21...28
AO1...AO8
29...34
NO1...6
29...34
35...39
IN1...5
40
IN6
Table 61 Description of mixed Panel Bus I/O module
terminals
ANALOG
GND
OUTPUTS
AO5 AO6 AO7
AO8
G1
G2
25 26 27
28
41
42
AO1 AO2 AO3 AO4
21 22 23 24
Comment
2-wire communication bus
(Panel Bus)
2-wire communication bus
(Panel Bus)
Power supply
Power supply
Binary inputs 1...7
Binary inputs 8...12
--
Analog inputs 1...8
Ground. Both grounds are
--
internally connected to each
other and to 24 VAC0.
--
Analog outputs 1...8
Relays 1...6, normally-open
contacts
Common contacts of relays
1...5. May be set to common
supply voltage via terminal 40
by inserting jumpers J1...J5 into
their lower positions. When, in
--
contrast, a jumper is in the
upper position (the so-called
"parking position" = default
setting), the corresponding relay
receives no supply voltage from
terminal 40.
Common contact of relay 6,
internally connected to the
--
middle contact of jumpers
J1...J5. May be used to connect
common supply voltage.
24 V RELAYS
J1
J2
JUMPER
JUMPER
JUMPER
IN1
IN2
IN3
35
R1
36
R2
37
R3
29
30
31
NO1
NO2
NO3
63
Description of the I/O Modules
J3
J4
J5
JUMPER
JUMPER
IN4
IN5
IN6
38
R4
39
R5
R6
40
32
33
34
NO4
NO5
NO6
EN1Z-0921GE51 R0709
COM
75
A
COM
76
B
24
77
V~
24
78
V~0
EXT. 24VAC FOR
RELAY COMMON