Carrier 50KC04-06 Service And Maintenance Instructions page 47

Single package rooftop electric cooling units with optional electric heat with refrigerant
Table of Contents

Advertisement

Table 15 — Dry Bulb Operation With DCV (CO
DEMAND
CONTROLLED
VENTILATION (DCV)
Below CO
set
2
Above CO
set
2
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
Table 16 — Enthalpy Operation Without DCV (CO
DEMAND
CONTROLLED
VENTILATION (DCV)
NONE
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
Table 17 — Enthalpy Operation With DCV (CO
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION (DCV)
ECONOMIZE
Below CO
set
2
Above CO
set
2
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I and
Y2–I have not been satisfied.
OUTSIDE AIR
GOOD TO
Y1-I
Y2-I
ECONOMIZE
Off
Off
No
On
Off
On
On
Off
Off
On
Off
Yes
On
On
Off
Off
No
On
Off
On
On
Off
Off
Yes
On
Off
On
On
OUTSIDE AIR
GOOD TO
Y1-I
Y2-I
ECONOMIZE
Off
Off
No
On
Off
On
On
Off
Off
On
Off
Yes
On
On
Y1-I
Y2-I
Off
Off
On
Off
No
On
On
Off
Off
On
Off
Yes
On
On
Off
Off
On
Off
No
On
On
Off
Off
On
Off
Yes
On
On
Sensor) — 1 Speed Fan
2
FAN SPEED
Y1-O
High
0-v/Off
High
24-v/On
High
24-v/On
High
0-v/Off
High
0-v/Off
High
24-v/On
High
0-v/Off
High
24-v/On
High
24-v/On
High
0-v/Off
High
0-v/Off
High
24-v/On
Sensor) — 1 Speed Fan
2
FAN SPEED
Y1-O
High
0-v/Off
High
24-v/On
High
24-v/On
High
0-v/Off
High
0-v/Off
High
24-v/On
Sensor) — 1 Speed Fan
2
FAN
Y1-O
Y2-O
SPEED
High
0-v/Off
0-v/Off
High
24-v/On
0-v/Off
High
24-v/On
24-v/On
High
0-v/Off
0-v/Off
High
0-v/Off
0-v/Off
High
24-v/On
0-v/Off†
High
0-v/Off
0-v/Off
High
24-v/On
0-v/Off
High
24-v/On
24-v/On
High
0-v/Off
0-v/Off
High
0-v/Off
0-v/Off
DELAY*
High
0-v/Off†
24-v/On
47
Y2-O
OCCUPIED
0-v/Off
VENTMIN
0-v/Off
VENTMIN
24-v/On
VENTMIN
0-v/Off
VENTMIN
VENTMIN to
0-v/Off
Full-Open
VENTMIN to
0-v/Off*
Full-Open
VENTMIN to
0-v/Off
VENTMAX
VENTMIN to
0-v/Off
VENTMAX
VENTMIN to
24-v/On
VENTMAX
VENTMIN to
0-v/Off
VENTMAX
VENTMIN to
0-v/Off
Full-Open
VENTMIN to
0-v/Off*
Full-Open
Y2-O
OCCUPIED
0-v/Off
MIN POS
0-v/Off
MIN POS
24-v/On
MIN POS
0-v/Off
MIN POS
MIN POS to
0-v/Off
Full-Open
MIN POS to
0-v/Off*
Full-Open
OCCUPIED
UNOCCUPIED
VENTMIN
VENTMIN
VENTMIN
VENTMIN
VENTMIN to
Full-Open
VENTMIN to
Full-Open
VENTMIN to
VENTMAX
VENTMIN L to
VENTMAX
VENTMIN H to
VENTMAX
VENTMIN L to
VENTMAX
VENTMIN to
Full-Open
VENTMIN to
Full-Open
UNOCCUPIED
Closed
Closed
Closed
Closed
Closed to
Full-Open
Closed to
Full-Open
Closed
Closed
Closed
Closed
Closed to
Full-Open
Closed to
Full-Open
UNOCCUPIED
Closed
Closed
Closed
Closed
Closed to
Full-Open
Closed to
Full-Open
Closed
Closed
Closed
Closed
Closed to
Full-Open
Closed to
Full-Open
Closed
Closed
Closed
Closed
Closed to
Full-Open
Closed to
Full-Open