Download Print this page

Honeywell 4000 Series Product Data page 8

Direct coupled valve actuators
Hide thumbs Also See for 4000 Series:

Advertisement

FIG. 11 — ML7984 WIRING WITH ELECTRONIC SERIES 90 "SUPERMOD" CONTROLLERS
ELECTRONIC
2 ML7984
SERIES 90
(W973, T775,
B
H775, W7100)
R
R
W
W
NOTE:
2 ML7984
Polarity sensitive,
check connections
W to R, R to W
B
R
R
W
W
2 ML7984
B
R
R
W
W
FIG. 11A — ML7984 WITH COMMON TRANSFORMER,
INDIVIDUAL CONTROLLERS
FUNCTION
1101
Electronic Series 90
Direct Acting
1111
Electronic Series 90
Reverse Acting
For Figures 11A and 11B the following apply:
Power supply provides overload protection and disconnect means.
1
Allow up to 0.5 amps for each device. Actuators and controller can share same transformer providing the VA rating of the
2
transformer is not exceeded and proper phasing is observed. Do not mix a.c. and d.c. power sources.
Do not mix M984/6 or Modutrol Motors with the ML7984 in the same circuitry.
3
Use configuration DIP switches to select device functions: Direct acting function (actuator stem moves upwards with
4
signal increases to 10V/20mA) or Reverse acting function (actuator stem moves downwards with signal increases to 10V/
20mA).
5
Turn power off before setting the DIP switches.
3
T6
T5
3
1
T6
24 Vac
T5
OR
3
T6
28 Vdc
T5
T6
T5
DIP SWITCH CONFIGURATION
1
2
3
1
2
3
ELECTRONIC
SERIES 90
(W973, T775,
H775, W7100)
R
L1
L2
W
NOTE:
Polarity sensitive,
check connections
W to R, R to W
FIG. 11B — ML7984 WITH INDIVIDUAL
TRANSFORMERS, COMMON CONTROLLER
On (1)
4
Off (0)
4
On (1)
5
Off (0)
4
8
2 ML7984
3
B
1
R
T6
24 Vac
W
T5
2 ML7984
T6
3
T5
B
1
R
T6
24 Vac
W
T5
T6
2 ML7984
3
T5
B
1
R
T6
24 Vac
T5
W
T6
T5
95C-10939-4
L1
L2
OR
28 Vdc
L1
L2
OR
28 Vdc
L1
L2
OR
28 Vdc