8.2
AC reactor
Always connect one AC reactor to one power regeneration converter unit.
The AC reactor generates heat of 100 higher than the ambient temperature. Fully consider heat dissipation, installation
position, wires used, etc., before installing the AC reactor.
Magnetism generated from the AC reactor may affect other devices. Leave a clearance of 100 mm or more around wires so
that they do not contact the AC reactor.
Specifications
Model
Rated capacity [kW]
Rated voltage
Rated current [A]
Frequency
Environment
Ambient
temperature
Ambient
humidity
Ambience
Altitude
Vibration resistance
Loss [W]
Mass [kg]
MR-AL-55K4-L
55
380 V AC to 480 V AC (power fluctuation ratio: within ±10%)
106
50 Hz/60 Hz (frequency fluctuation: within ±3%)
Operation
0 to 55 (non-freezing)
-20 to 65 (non-freezing)
Storage
Operation
5 %RH to 90 %RH (non-condensing)
Storage
Indoors (no direct sunlight), no corrosive gas, inflammable gas, oil mist, dust, or conductive particle
2000 m or less above sea level
2
5.9 m/s
or less
330
56
8 OPTIONS AND PERIPHERAL EQUIPMENT
8.2 AC reactor
8
67