Troubleshooting

If for any reason the pressurisation unit does not seem to be functioning correctly, please refer to the table
below for a list of solutions to known problems.
If the pressurisation unit is showing a fault code on the display, holding down the [SET] button will
cause the current system pressure to be temporarily shown on the display.
Fault Finding
• Check electrical supply.
• Check for external controls affecting the unit.
• If the pump is running continuously:
Either the system is not full (possibly a leak)
Check the pump pressure switch operation
Check the Pressure Reducing Valve operation
• If the pump does not run:
Check the pump pressure switch operation
Check the pump operation
Check the internal filter within the break tank is present and clear
• If the unit fails to pressurise the system:
Check the system connection valve is open
The operation of the break tank float valve that there is water available in the break tank
Check the internal filter within the break tank is clear
Check for system leaks
• For intermittent running, but normal when pressurising, check for system leaks
• If the system over-pressurises:
Check the operation of the pump pressure switch
Check the operation of the Pressure Reducing Valve (if fitted)