Maximum Vent Length Table; Upflow/ Hprizontal Venting Table; Vent And Inlet Air Connections - Trane AUH1B040A9241A Installer's Manual

Upflow/horizontal, downflow/horizontal, gas-fired, direct vent condensing furnaces
Hide thumbs Also See for AUH1B040A9241A:
Table of Contents

Advertisement

15 minutes before handling. Cure time varies according
to fit, temperature and humidity.
NOTE:
Follow venting instructions carefully when using PVC cement.
IMPORTANT:
All joints must be water tight. Flue condensate is somewhat
acidic, and leaks can cause equipment damage.
Connection of the pipe and collar of the combustion air
inlet should just be a friction fit. It is recommended that
the inlet air joint be sealed with RTV type sealant to allow
the joint to be separated for possible future service. The in-
let and vent pipes must be properly supported throughout
the entire length.
Connection of the vent pipe to the vent collar should also
be accomplished using RTV type sealant. This type sealant
provides a connection which remains flexible and can be
separated in the future if service needs require the removal
of the vent pipe for service or clearance. See Figure 24.
NOTE:
To ensure proper operation at the vent lengths indicated,
the combustion air inlet and vent terminals should be in
the same pressure zone. Terminating the vent and inlet in
different pressure zones will change the maximum vent
lengths and may cause nuisance tripping of the pressure
switch(es). The amount of change can not be predicted.
The selection of the inlet and outlet terminal locations are
the responsibility of the designer/installer. If the installer
chooses separate pressure zones for the terminals, the
combustion air inlet termination must be in the higher
(more positive) pressure zone.
MAXIMUM VENT LENGHT TABLE
MAXIMUM VENT LENGTH:
2" PIPE
& FITTINGS
MODEL
*UH1B040A9241A
60
*UH1B060A9361A
60
*UH1B080A9421B
40
*UH1C080A9601A
NOT ALLOWED
*UH1C100A9481A
NOT ALLOWED
*UH1D100A9601A
NOT ALLOWED
*UH1D120A9601A
NOT ALLOWED
NOTES: * - First letter may be "A" or "T"
1. FOR DURAVENT MANUFACTURED MODULAR VENTING SYSTEMS THAT ARE APPROVED IN TABLE 10, EQUIVALENT VENT LENGTHS MAY BE DIF-
FERENT FROM WHAT IS SHOWN ABOVE. REFER TO THE VENTING SYSTEM MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR APPROPRIATE
VENTING DIAMETERS AND EQUIVALENT LENGTHS.
2. Minimum vent length for all models: 3' horizontal or 3' vertical.
3. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace). If different
inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See note 6 below for exception). The inlet pipe
can be of a larger diameter, but never smaller than the vent pipe.
4. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent
or Inlet air pipes).
5. One SHORT radius 90° elbow is equivalent to 10' of 4" pipe, 10' of 3" pipe, or 8' of 2" pipe. One LONG radius elbow is equivalent to 6' of 4" pipe, 7' of 3" pipe, 6'
of 2.5" pipe, or 5' of 2" pipe. Two 45° elbows equal one 90° LONG elbow.
6. The termination tee or bend must be included in the total number of elbows. If the BAYAIR30AVENTA termination kit is used, the equivalent length of pipe is 5
feet. BAYVENT200B equivalent length is 0 feet.
7. Pipe adapters are field supplied (except for the *UH/DH2D120 models).
8. For Canadian applications, venting systems must meet ULC-S636 requirements.
18-CD29D1-11
UPFLOW/ HORIZONTAL VENTING TABLE
DIRECT VENT (2 PIPE SYSTEM) -
MAXIMUM TOTAL EQUIVALENT FEET FOR
VENT AND INLET AIR PIPES (See Notes)
2-1/2" PIPE
3" PIPE
& FITTINGS
& FITTINGS
80
100
80
100
80
100
NOT ALLOWED
70
NOT ALLOWED
90
NOT ALLOWED
90
NOT ALLOWED
50
Installer's Guide
L
CARBON MONOXIDE POISONING HAZARD
FAILURE TO FOLLOW THE DURAVENT INSTALLATION
INSTRUCTIONS IF THE POLYPROPELENE VENTING
SYSTEM IS BEING PLACED INTO OPERATION COULD
RESULT IN CARBON MONOXIDE POISONING OR DEATH.

VENT AND INLET AIR CONNECTIONS

f
Seal INLET AIR PIPE
with RTV sealant
Products installed in Canada must use vent systems
that are certified to the Standard for Type BH Gas Vent-
ing Systems (ULC S636) for Class II-A venting systems
(up to 65°C). Components of the vent system must not
be interchanged with other vent systems or unlisted
pipe or fittings. Plastic components, specified primers,
and glues must be from a single system manufacturer
and not intermixed with other system manufacturer's
vent system parts. In addition, the first three feet of the
vent pipe must be visible for inspection.
TABLE 11
NONDIRECT VENT (1 PIPE SYSTEM) -MAXIMUM TOTAL
4" PIPE
2" PIPE
& FITTINGS
& FITTINGS
130
50
130
50
130
30
130
NOT ALLOWED
130
NOT ALLOWED
130
NOT ALLOWED
130
NOT ALLOWED
WARNING
!
Seal VENT PIPE
with RTV sealant
Front of Furnace
EQUIVALENT FEET FOR
VENT PIPE ONLY (See Notes)
2-1/2" PIPE
3" PIPE
& FITTINGS
& FITTINGS
80
80
80
80
80
80
NOT ALLOWED
50
NOT ALLOWED
70
NOT ALLOWED
70
NOT ALLOWED
30
4" PIPE
& FITTINGS
130
130
130
130
130
130
130
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents