Binary Input; A.5.2 Binary Input - Siemens SIPROTEC 7ST6 Manual

Numerical overhead contact line protection for ac traction power supply
Table of Contents

Advertisement

A.5.2

Binary Input

Table A-2
Table A-3
7ST6 Manual
E50417-G1176-C251-A3
Binary input presettings for all devices and ordering variants
Binary Input
Allocated Func-
tion
BI1
>FAIL:Feeder VT
BI2
>VT MCB UF
BI3
>Reset LED
BI4
>Dis.Z1 act.
BI5
>DisZ1str act
BI6
>Dis. Z2 act.
BI7
>DisZ2str act
BI8
>Dis Z3 act
BI9
>Dis Z3str act
BI10
>Cat.1 active
BI11
>Cat.2 active
BI12
>Cat.3 active
Further binary input presettings for 7ST63*
Binary Input
Allocated Func-
tion
BI13
>Ctrl Select.
BI15
>Time Synch
BI17
>Set Group Bit0
BI18
>Set Group Bit1
BI20
>CB-TEST
BI21
>CB-TEST AR
BI22
>Brk Aux NO
BI23
>Brk Aux NC
BI24
>CB Ready
BI26
>AR ON
BI27
>AR OFF
BI28
>Sync. on
BI29
>Sync. off
Function No.
361
>Failure: Feeder VT (MCB tripped)
13951
>U feeder side VT MCB tripped
5
>Reset LED
3901
>Dist.: Zone Z1 is active
3900
>Dist.: Zone Z1 stroke is active
3903
>Dist.: Zone Z2 is active
3902
>Dist.: Zone Z2 stroke is active
3907
>Dist.: Zone Z3 active
3906
>Dist.: Zone Z3 stroke active
6605
>First catenary is active
6604
>Second catenary is active
6603
>Third catenary is active
Function No.
365
>Select: Control by BI or SYS inter-
face
3
>Synchronize Internal Real Time
Clock
7
>Setting Group Select Bit 0
8
>Setting Group Select Bit 1
13860
>CB-Test: Start TRIP cycle
13861
>CB-Test: Start TRIP-CLOSE cycle
4601
>Breaker contact (OPEN, if bkr is
open)
4602
>Breaker contact(OPEN, if bkr is
closed)
2730
>Circuit breaker READY for reclosing
2701
>Auto reclose ON
2702
>Auto reclose OFF
2901
>Switch on synchro-check function
2902
>Switch off synchro-check function
A.5 Default Settings