Code
Name
+ATR3
Additional mono-
phase auxiliary
transformer power
rating
+SPD412
AC standard surge
protection device
Type I + II 400V
+SPD812
AC standard surge
protection device
type I + II 800V
+MCB
Main circuit breaker
+M24CCV
SafeRing CCV mod-
ule
+M36CCV
SafeRing CCV mod-
ule
+M2420
SafeRing module
+M3625
SafeRing module
+MMOTO
Motorized V module
+MREF6
Feeder protection
and control relay
REF615
+MREFS
Feeder protection
and control relay
REF615 and AC MV
metering
+TRFENCE
Transformer fence
+C5M
C5-M corrosion pro-
tection
degree
for enclosure
+SIGC
Signal concentration
+COM2
Basic
communication
board 1
+COM1
Basic
communication
board 2
+FRADD
French add-ons
+HVBOX
MV bushing
protection box
Description
An additional auxiliary monophase service transformer of 3kVA is in-
stalled to provide customer with specified voltage level and frequency
Standard surge protection device type II is replaced with standard surge
protection device type I + II. Only applicable for PVS-100/120 solutions
Standard surge protection device type II is replaced with standard surge
protection device type I + II. Only applicable for PVS-175 solutions
Addition of a main circuit breaker
MV switchgear
Standard 24kV CV SafeRing switchgear is replaced with SafeRing CCV
switchgear only for RMU 24kV RMU
Standard 36kV CV SafeRing switchgear is replaced with SafeRing CCV
switchgear only for RMU 36kV RMU
SafeRing switchgear 24kV 16kA is replaced with SafeRing switchgear
24kV 20 kA only for RMU 24kV RMU
SafeRing switchgear 36kV 20kA is replaced with SafeRing switchgear
36kV 25 Ka only for RMU 36kV RMU and 50 Hz
Manual V module is replaced with motorized V module
Standard self-powered protection relay REJ603 is replaced with extens-
ive protection relay REF615. Including current transducers (voltage
protection not included in this option)
Standard self-powered protection relay REJ603 is replaced with extens-
ive protection relay REF615 and combisensors for
measuring and voltage protections
Station (skid)
Supply of a transformer fence around the transformer perimeter
Enclosure and MV transformer standard C4 corrosion degree is up-
graded to C5M corrosion degree Also select the upgrade of C5 protec-
tion for the oil transformer (+ TRC5). This option is
recommended for sites near sea (>10 km).
Concentration of all the signals of the station in one point
Communication board for projects of 1 station
Communication board for projects of >1 station, for communication
between stations
Metallic cable glands an MV bushing interlocking system
Installation of a HV box to protect the HV bushings of the
transformer