Example No. 2; Example No. 3 - Siemens Cerberus GW-21 Technical Manual

Lmsmodular gateway
Table of Contents

Advertisement

Siemens Building Technologies
Cerberus Division
7.2

Example no. 2

In this second example, the gateway is configured for four subsystems and two moni-
toring stations:
§ first central station LMS (master)
§ second central station LMS (slave)
§ 4 subsystems
§
§
§
Setting of DIL-Switches:
DIL-Switch
UART 1
S1.4
S1.5
S1.6
UART 2
S2.2
S2.3
S2.4
UART 3
S2.8
S3.1
S3.2
UART 4
S3.6
S3.7
S3.8
UART 5
S4.5
S4.6
S4.7
UART 6
S5.3
S5.4
S5.5
Tab. 11
Remember that when your system needs two LMS stations, you must configure them
using UART 1 (as a master station) and UART 2 (as a slave station).
UART 1
UART 2
CS11
UART 3
CS11
UART 4
CS4
UART 5
CS4
UART 6
subsystem
ON
LMS master
ON
ON
ON
LMS slave
ON
ON
ON
CS11
OFF
OFF
ON
CS11
OFF
OFF
OFF
CS4
ON
OFF
OFF
CS4
ON
OFF
network address
0
1
2
3
21
E1481b
06.2000