CHECK OUTPUT
Process Variables
Sensor Temperature
3-8
Before performing other transmitter on-line operations, review the digital
output parameters to ensure that the transmitter is operating properly and is
configured to the appropriate process variables.
The process variables for the 2051 provide transmitter output, and are
continuously updated. The pressure reading in both engineering units and
percent of range will continue to track with pressures outside of the defined
range from the lower to the upper range limit of the sensor module.
HART Communicator
4-20 mA Fast Keys
1-5 Vdc Fast Keys
The process variable menu displays the following process variables:
•
Pressure
•
Percent of range
•
Analog output
AMS Device Manager
Right click on the device and select "Process Variables..." from the menu.The
process variable screen displays the following process variables:
•
Pressure
•
Percent of range
•
Analog output
The 2051 contains a temperature sensor near the pressure sensor in the
sensor module. When reading this temperature, keep in mind the sensor is
not a process temperature reading.
HART Communicator
4-20 mA Fast Keys
1-5 Vdc Fast Keys
Enter the fast key sequence "Sensor Temperature" to view the sensor
temperature reading.
AMS Device Manager
Right click on the device and select "Process Variables..." from the menu.
"Snsr Temp" is the sensor temperature reading.