Maintenance; Testing Co And Co 2 - Worcester GREENSTAR HE combi Series Installation And Servicing Instructions

Wall mounted condensing boiler for central heating and mains fed domestic hot water
Table of Contents

Advertisement

Maintenance

In "chimney sweep" mode, the appliance
i
switches to max. rated heat output or the
set heating output. You then have 15 min-
utes in which to measure the levels. After
that, the appliance switches back from
"chimney sweep" mode to normal mode.
B Remove sealing plug from combustion air testing
point (234.1, fig. 48).
B Insert testing probe about 80 mm into the testing
point and seal testing point.
Fig. 48
B Measure O
and CO
2
2
B Refit sealing plug.
B Press and hold
button until the display shows – –.
The
button will stop flashing and the display
shows the CH flow temperature.
7.2.2
Testing CO and CO
B Press and hold the
shows – –.
"Chimney sweep" mode is now active.
The
button will light up and the display shows the
CH flow temperature.
You have 15 minutes in which to measure
i
the levels. After that, the appliance switch-
es back from "chimney sweep" mode to
normal mode.
B Remove sealing plug from flue gas testing point
(234, fig. 48).
B Insert testing probe about 135 mm into the testing
point and seal testing point.
B CO- and CO
levels.
2
B Refit sealing plug.
B Press and hold
button until the display shows – –.
The
button will stop flashing and the display
shows the CH flow temperature.
32
levels.
2
button until the display
8
Maintenance
B Always disconnect the appliance from
the electrical power supply (fuse, circuit
breaker) before carrying out any work
on the electrical systems or compo-
nents.
B Always turn off the gas cock before car-
rying out any work on components
which carry gas.
There is a Service booklet for the Engi-
i
neer, order no. 7 181 465 346, available
to competent persons.
All safety and control systems are moni-
i
tored by the Bosch Heatronic. In the event
of a component fault, the display shows a
fault code.
B The User should be recommended to have the appli-
ance serviced regularly by a competent person (see
Maintenance Contract).
B Use only genuine spare parts
B Refer to the Spare Parts List when ordering spare
parts.
B Always renew seals and O-rings removed during
servicing or repair work.
B Use only the following types of grease:
– Water valve: WRc approved silicon based grease
– Unions: approved sealant.
B To drain the appliance shut the system valves and
open the pressure relief valve.
B Upon completion of any electrical work check for
earth continuity, correct polarisation and resistance
to earth.
6 720 610 576 GB (03.02)