Domestic Hot Water Heat Exchanger; Electrode Assembly - Worcester GREENSTAR HE combi Series Installation And Servicing Instructions

Wall mounted condensing boiler for central heating and mains fed domestic hot water
Table of Contents

Advertisement

8.3.8

Domestic Hot Water Heat Exchanger

B Refer to section 7.2.
B Use new seals when fitting the new heat exchanger.
8.3.9

Electrode assembly

B Refer to section 7.2.
B Use a new seal if the existing seal is damaged.
8.3.10 Pressure gauge
B Drain the appliance.
B Lower the facia. Refer to fig. 62.
B Twist the pressure gauge head anti-clockwise to
release it from the casing. Refer to fig. 2.
B Disconnect the capillary head from the rear of the
diverter valve by withdrawing the clip and pulling out
the head. Refer to fig. 63.
8.3.11 Expansion vessel
B Drain the appliance.
B Undo the union connection at the base of the vessel.
Refer to fig. 2.
B Unscrew the top and bottom fixing screws and
remove the vessel.
B Set the pressure of the new vessel to that required
by the system.
8.3.12 Pressure Relief Valve
B Drain the appliance.
B Disconnect the drain pipe from the valve. Refer to
fig. 30.
B Pull-out the clip securing the valve.
B Pull-out the valve.
B Ensure that the replacement valve is fully entered
before fitting the clip.
8.3.13 Burner
B Refer to section 8.2.
6 720 610 576 GB (03.02)
8.3.14 Flow switch
B Shut the mains water inlet valve and drain the domes-
tic hot water circuit.
B Pull-off the connectors from the micro-switch.
B Unscrew the inlet and union connection and remove
the assembly.
B Reset the domestic hot water flow rate on the new
assembly.
INLET
6 720 610 602 - 05.10
Fig. 65
Maintenance
OUTLET
41